HA40 4-Channel Controller
HA40 Technical Manual
1-5
1.3.6 Housings / Installation Categories
*NEMA 4X wall mount. DIV 2 Groups A,B,C,D; Category II and •
pollution degree 3; NEMA 4X; IP66*NEMA 7 wall mount for DIV
1 & 2 Groups B,C,D; includes • o-ring in door to satisfy NEMA 4
rating.*Includes standard non-intrusive magnetic keypad.
1.3.7 Approvals
CSA C22.2 No 1010.1 and ISA S82.02•
CSA C22.2 No 152 for combustibles using mA input
UL 1604/C22.2 No. 213 (Div 2 Groups A,B,C,D)
EN55011 & EN61000 (CE Mark) CSA File # = 219995
1.3.3 Ambient Temperature Range
-25 to 50 degrees C
1.3.4 Humidity Range
0 to 90% R. H. Non-Condensing.
1.3.5 Altitude
Recommended up to 2000 meters
1.3.6 Housings / Installation Categories
• *NEMA 4X wall mount. DIV 2 Groups A,B,C,D; Category II and
pollution degree 3; NEMA 4X; IP66
• *NEMA 4 painted carbon steel
• SS316 NEMA4X
• Polycarbonate NEMA4X
• *NEMA 7 wall mount for DIV 1 & 2 Groups B,C,D; includes
O-ring in door to satisfy NEMA 4 rating.
*Includes standard non-intrusive magnetic keypad.
1.3.7 Approvals
• CSA C22.2 No 1010.1 and ISA S82.02
• CSA C22.2 No 152 for combustibles
• UL 1604 / C22.2 No 213 (Div 2 Groups A,B,C,D)
• EN55011 & EN61000 (CE Mark). CSA File # = 219995 and
may be seen at:
www.CSA-International.org
.
Summary of Contents for HA40
Page 6: ...HA40 4 Channel Controller HA40 Technical Manual 1 1 1 General Description ...
Page 11: ...HA40 4 Channel Controller HA40 Technical Manual 2 1 2 Operation ...
Page 21: ...HA40 4 Channel Controller HA40 Technical Manual 2 11 ...
Page 22: ...HA40 4 Channel Controller HA40 Technical Manual 3 1 3 Motherboard Interface PCB ...
Page 31: ...HA40 4 Channel Controller HA40 Technical Manual 4 1 4 Enclosures ...
Page 34: ...HA40 4 Channel Controller HA40 Technical Manual 5 1 5 Parts List ...
Page 36: ...HA40 4 Channel Controller HA40 Technical Manual 6 1 6 Specifications ...
Page 38: ...HA40 4 Channel Controller HA40 Technical Manual 7 1 7 Warranty ...