WIRING
Humidifier 69-2413EF—09
22
Honeywell HumidPRO
TM
Frost Index
Installer System Test/Checkout
Outdoor Temp
-10
°
F
0
°
F
10
°
F
20
°
F
30
°
F
40
°
F
Fr
ost
Index
1
10
10
10
10
11
11
17
17
25
25
35
36
2
10
10
10
10
15
15
21
21
29
29
35
39
3
10
10
14
14
19
19
26
26
34
34
35
46
4
15
15
19
19
25
25
32
32
35
39
35
52
5
21
21
26
26
32
32
35
38
35
48
35
58
6
29
29
34
34
35
39
35
48
35
56
35
60
7
35
39
35
46
35
52
35
58
35
60
35
60
8*
35
56
35
60
35
60
35
60
35
60
35
60
9
35
60
35
60
35
60
35
60
35
60
35
60
10
35
60
35
60
35
60
35
60
35
60
35
60
*Black Numbers show highest humidity allowed when Default RH% (35%) is Selected.
Note: Smaller grey numbers show highest humidity allowed when Maximum RH% (60%) is selected.
Press
p
/
q
to turn system on/off.
Press
NEXT
to advance to next test.
Press
DONE
to terminate system test.
To begin,
press and hold
the
p
and
q
buttons until the display changes.
Function Number
Setting
Number
Description
10
System Test
0
OFF
1
ON
20
View Outdoor Temperature
Shows Outdoor Temperature
10
0
M29388A
Test number
System status
NOTE: Most humidifiers require airflow in the system to operate. Make sure to turn on the system fan when
testing humidifier operation.
H6062 Specifications
Humidity Ranges:
Humidify:
• Default: 10% to 60%
• Total Range Available: 10% to 90%
Operating Ambient Temperature
•
32° to 120°F (0° to 48.9°C)
Operating Relative Humidity
• 5% to 90% (non-condensing)