HE225 BYPASS FLOW-THROUGH HUMIDIFIER

3

69-1425EF—01

3

69-1425EF—03

Template (entire sheet) Top of Humidifier

Te

mp

late (en

tire 

sheet

)

Te

mp
late (en

tire 
sh
eet
)

Template (entire sheet)

For humidity control wiring connections:

1.

Wire the humidifier solenoid valve, current sensing relay or sail 

switch, humidity control and transformer. Refer to the humidity 

control installation instructions for mounting and wiring 

information.

IMPORTANT 

• For proper operation, the humidifier must be energized

during blower motor cycles.

• Current sensing relay or sail switch is not needed with the 

Automatic Humidity Control.

NOTE: Select models of fan centers include humidifier taps so the 

current sensing relay or sail switch are not needed.

PLUMBING SADDLE VALVE

Hot or cold water, either hard or softened, can be used in the 

humidifier. 

1.

Use the self-piercing saddle valve (included) to tap into the 

water supply line at an appropriate location.

WARNING

Chemical Hazard.

Can cause personal injury or equipment damage.

Do not use any line connected to an air conditioner.

IMPORTANT

• The saddle valve is not designed to be used to regulate water 

flow. The valve is either open or closed.

• To prevent debris from clogging the solenoid in-line filter, be 

sure to install the saddle valve handle pointing toward the 

ceiling.

NOTE: Lightly clean the copper tubing ends with fine sand-

paper before making any connections.

2.

Use 1/4 in. O.D. copper tubing and connect the saddle valve to 

the inlet side of the solenoid valve.

a. Place the brass compression nut over the copper tubing.

b. Slide the brass ferrule over the tubing. 

NOTE: Do not over-tighten the compression nut. Moderate 

tightness will prevent leaking. 

c. Insert the tubing into the solenoid valve fitting and support 

the valve while tightening the compression nut. 

NOTE: Slope drain tube downward for correct drainage.

3.

Connect a 1/2 in. drain tube to the humidifier drain fitting and run 

to a suitable drain.

CHECKOUT

1.

Open the saddle valve.

NOTE: The furnace blower must be on for the humidifier to 

operate.

2.

Set the thermostat setpoint 10°F (6°C) above the room 

temperature.

3.

Set the Humidity Control to a high humidity setting, or place the 

setting in the test position.

4.

Observe the water running out of the drain line to be sure the 

humidifier is working properly.

5.

Check for leaks.

6.

Reset the Humidity Control to a comfortable setting, or the 

Automatic Humidity Control to the desired frost factor setting.

Summary of Contents for HE225

Page 1: ... supply plenum static pressure is no greater than 0 3 in w and water pressure is no greater than 125 psi IMPORTANT To assure optimal product performance be sure the template is level before marking 1 Determine the best location for the humidifier and draw a level line on the plenum See Fig 1 Fig 1 Typical humidifier installation locations IMPORTANT Mount the humidifier at least 3 in 76 mm above th...

Page 2: ...a 90 elbow attachment to the collar 11 Seal the duct connections with duct tape NOTE To avoid sagging and stress on the humidifier add support when ducting is longer than 4 ft 120 cm 12 Reinstall the humidifier pad assembly in the humidifier housing NOTE Be sure the water feed tube is not pinched or kinked 13 Hinge the cover in place and secure with the thumbscrew located at the bottom of the cove...

Page 3: ...er flow The valve is either open or closed To prevent debris from clogging the solenoid in line filter be sure to install the saddle valve handle pointing toward the ceiling NOTE Lightly clean the copper tubing ends with fine sand paper before making any connections 2 Use 1 4 in O D copper tubing and connect the saddle valve to the inlet side of the solenoid valve a Place the brass compression nut...

Page 4: ...ate entire sheet U S Registered Trademark 2010 Honeywell International Inc 69 1425EF 03 K K Rev 06 10 Printed in U S A Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com ...

Page 5: ...entation dans le plenum ne dépasse pas 0 3 po c e et que la pression de l eau ne dépasse pas 125 psi IMPORTANT Avant de marquer l emplacement vérifier si le gabarit est de niveau pour assurer le rendement optimal de l appareil 1 Déterminer l endroit le mieux approprié pour l humidificateur et tracer une ligne de niveau sur le plenum Voir la Fig 1 Fig 1 Emplacements types de l humidificateur IMPORT...

Page 6: ...oude de 90 doit être fixé au collet 11 Sceller les raccords de la gaine avec du ruban à gaine isolant REMARQUE Si la gaine mesure plus de 120 cm 4 pi de longueur installer des supports pour éviter son affaissement et les contraintes sur l humidificateur 12 Remettre l ensemble écran évaporateur dans le boîtier de l humidificateur REMARQUE S assurer que le tube d arrivée d eau n est ni écrasé ni tor...

Page 7: ...binet vanne doit être soit ouvert soit fermé S assurer que la poignée du robinet vanne à étrier pointe vers le plafond lors de l installation pour prévenir que des débris ne bloquent l électrovanne dans le filtre du tuyau REMARQUE Avant d effectuer les raccords nettoyer légèrement l extrémité des tuyaux avec un papier de verre fin 2 Utiliser un tuyau en cuivre de 1 2 de po de diamètre extérieur po...

Page 8: ...barit feuille entière Solutions de régulation et d automatisation Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com Marque de commerce déposée aux É U 2010 Honeywell International Inc Tous droits réservés 69 1425EF 03 K K Rev 06 10 Imprimé aux É U ...

Reviews: