4. Set Up and Calibration Procedures - Relays Set Up Group
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
39
7/07
Relays Set Up Group
ATTENTION
The Relay set up group parameters are accessible only if relay PWAs are installed in the
actuator. 10260S series actuators can be equipped with up to two relay PWAs –for a total of
four SPDT relays. Using the Relay set up groups you can program the installed relays to
operate in response to various operating conditions.
Table 11lists the parameters and selections available when the SET RELAY
n
group is selected.
Table 11 Relay Set Up Group Parameters
Lower Display
Prompt
Upper Display
Selections or
Range of Setting
Parameter Definition
RTYPny
n
= 1, 2, 3, or 4
y
= 1 or 2
NONE
[default]
or
InPR
PosR
DEV
ULim
LLim
T Hi
T Lo
STRT
STAL
MAN
PWRF
FsFA
PosF
DiGI
TDEG
RELAY TYPE
—Selects the relay number and the relay
activation type. See Table 12 Relay Type Descriptions.
Input Range
—Upper / lower limits of input signal exceeded
Position Range
—Upper / lower limits of motor position
exceeded
Deviation
—Deviation from input exceeded
Upper Limit Travel
—Same as PosR for upper limit
Lower Limit Travel
—Same as PosR for lower limit
Temperature High
—High temperature limit exceeded
Temperature Low
—Low temperature limit exceeded
Starts
—Motor starts limit exceeded
†
Allows setting of multiplier value.
Stalled
—Motor position does not follow input
Manual
—Actuator is set to manual mode
Power Up Test Failure
—Failure of any power up diagnostic
Failsafe Alarm
—Failsafe condition detected
Position Sensor Signal Failure
—NCS output out of valid
range
Digital Input
—Digital input closure
Total Degrees
—
total degrees traveled.
RnyE
9
†
X1
or
X10k
MULTIPLIER
—(Relay Type STRTS only) Selects the
multiplier for the number limit of motor starts before the relay
is activated. Multiplier specifies the value on display as
times one (X1) or times ten thousand (X10k).
RnyVALn
= 1,
2, 3, or 4
y
= 1 or 2
0.0 to 100.0
RELAY VALUE
—Sets numerical value of limit where relay
trips (energizes). Units are determined by the relay type
selection. See Table 12 Relay Type Descriptions for units.
Rny HLn
= 1, 2,
3, or 4
y
= 1 or 2
HILO RELAY
HIGH/LOW
—Sets relay trip point to high or low limit.
RLYnHY
n
= 1, 2, 3, or 4
0.0 to 100.0
(in percent)
RELAY HYSTERESIS
—0.0 to 100.0% of span or full output.
NOTE: Relay Hysteresis parameter is accessible only if
appropriate relay type is selected.
n
is the relay number,
y
is the relay contact.