4. Set Up and Calibration Procedures - Drive Set Up Group
50
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
Revision 5
7/07
Drive Set Up Group
Table 19 lists the parameters and selections available for the SET DRVINF group.
Table 19 Drive Set Up Group Parameters
Lower Display
Prompt
Upper Display
Selections or
Range of Setting
Parameter Definition
VERSON
Nnnn
FIRMWARE VERSION
—
Read Only.
Displays the firmware
version currently in use by the actuator’s CPU.
SPEED
(90
°
@ 60hz)
10s
20s
40s
60s
20s
40s
60s
40s
60s
STROKE SPEED
—
Read Only.
The speed is the number of
seconds it takes for the actuator shaft to move its full range
of travel.
SPEED
(90
°
@ 50hz)
12s
24s
48s
72s
24s
48s
72s
48s
72s
STROKE SPEED
—
Read Only.
The speed is the number of
seconds it takes for the actuator shaft to move its full range
of travel.
POWER
1206
1205
2206
2205
POWER INPUT VOLTAGE AND FREQUENCY
—
Read
Only.
Selects the power input voltage and line frequency of
the actuator.
1206
—120Volts, 60Hz
1205
—120Volts, 50Hz
2206
—220Volts, 60Hz
2205
—220Volts, 50Hz
TAG
Nnnnnn
TAG NAME
—Selects the tag name or identifier of the
actuator. Up to 6 alphanumeric characters. See “
Set Tag
Nam
e” on next page.
ROTATE
90
ROTATION
— Indicates the factory calibrated degrees of
rotation.
90
— Factory calibrated for 90 degrees of rotation.
TORQUE
10 lb-ft / 15 N-M
20 lb-ft / 27 N-M
40 lb-ft / 55 N-M
60 lb-ft / 80 N-M
40 lb-ft / 55 N-M
80 lb-ft / 110 N-M
150 lb-ft / 200 N-M
200 lb-ft / 270 N-M
300 lb-ft / 400 N-M
Motor Torque value