4. Set Up and Calibration Procedures -
54
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
Revision 5
7/07
Lower Display
Prompt
Upper Display
Selections or
Range of Setting
Parameter Definition
MANRST
NONE
STAL
STRT
REGNn
n
= 0 to 9
TEMP
TDEG
RELn
n
= 1, 2, 3 or 4
ALL
SYST
MAINTENANCE STATISTIC RESET
—Allows reset of the
following maintenance statistics:
None
—No reset of maintenance statisitics
Stall
—Resets accumulated stall time to zero.
Motor Starts
—Resets accumulated motor start counts to
zero.
Motor Starts in the Region
—Resets to zero the
accumulated motor starts for
n
th
10% of motor span.
Temperature Statistics
—Resets the high / low temperature
limit statistics to zero.
Total Degrees
—Resets the total degrees of motor travel to
zero.
Relay Counts
—Resets accumulated relay cycle counts to
zero for the relay option number displayed.
All
—Resets all maintenance statistics to zero.
System Restart--Enables the system restart function
LD CAL
NONE
[default]
INP
MTR
COUT
ALL
POS
RESTORE CALIBRATION TYPE
—Allows you to restore a
calbration value to its factory calibration.
Input
—Restores input calibration to the factory calibration.
Motor
—Restores motor calibration to the factory calibration.
Output
—Restores actuator output calibration to the factory
calibration. For 4-20 mA output only; all other CUROUT
selections require output calibration.
All
—Restores input, motor and output calibration to the
factory calibrations.
Position Sensor
—Restores position sensor calibration to
the factory calibration.
NOTE: Allows a position sensor field calibration to be stored
as a factory calibration. This is to be used after replacement
of the sensor in the field. See “
Calibrate POS Output
”.
LD CFG
DIS
ENAB
RESTORE DEFAULT FACTORY CONFIGURATION
---
Allows you to restore the factory default configuration values.
DIS
--- Restore disabled.
ENAB
--- Restore enabled.
RESTRT DIS
ENAB
SYSTEM RESTART
--- Allows you to force the system to go
thru a restart.
DIS
--- Restart disabled.
ENAB
--- Restart enabled.
Note: The
MANRST
function must be set to
SYST.
* Temperature units are displayed in degrees C or F, and are set by the UNITS parameter. See SET
DISPLA set up group.
†
Note that the upper display contains the parameter name and the lower display contains the value.
This is to allow for the display of hours: minutes: seconds.