6. Control Applications - Master/Slave Arrangement
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
81
7/07
Hot
10260S Series Actuator #1
Neutral
Ground
120/240
VAC
250 Ohms
1 to 5 VDC
+
-
Current Output Controller
4 to 20 mA
Hot
10260S Series Actuator #2
Neutral
Ground
120/240
VAC
250 Ohms
1 to 5 VDC
Hot
10260S Series Actuator #3
Neutral
Ground
120/240
VAC
250 Ohms
1 to 5 VDC
Preferred
Wiring
Note: Controller must
be capable of sourcing
the impedance.
NOTE: If using HART communications, for this application HART must be configured for Multi-drop operation.
Hot
10260S Series Actuator #1
Neutral
Ground
120/240
VAC
250 Ohms
1 to 5 VDC
+
-
Current Output Controller
4 to 20 mA
Hot
10260S Series Actuator #2
Neutral
Ground
120/240
VAC
Hot
10260S Series Actuator #3
Neutral
Ground
120/240
VAC
Alternate
Wiring
NOTE: If using HART communications, for this application HART must be configured for Multi-drop operation.
Figure 28 Multiple Actuator Interconnection Diagrams