Set Up and Calibration Procedures
Calibration
Revision 7
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
69
7/08
Table 25 Input Calibration Procedure
Step
Operation
Press
Result
1
Enter Calibration
Mode
SETUP
until you see
Upper Display
=
CAL
Lower Display
=
INPUT
FUNCTION
Upper Display
=
DIS
Lower Display
=
CAL IN
or
key
Upper Display
=
BEGN
Lower Display
=
CAL IN
2
Calibrate Zero (0%)
FUNCTION
Upper Display
=
APLY
Lower Display
=
INZERO
•
Adjust the signal source to an output value equal to 0% range
value.
•
Wait 5 seconds, then go to step 3.
3
Calibrate Span
(100%)
FUNCTION
Upper Display
=
APLY
Lower Display
=
INSPAN
•
Adjust the signal source to an output value equal to 100%
range value.
•
Wait 5 seconds, then go to step 4.
4
FUNCTION
Calibration for zero and span input values are now saved. Input
calibration is complete.
NOTE: The display will automatically go to the CAL MOTOR set
up display. See Table 26. You may also exit calibation mode by
pressing the DISPLAY or SETUP keys.
ATTENTION:
When calibrating the motor to a short stroke range, you must
reset the end-of-travel limit switches. See
Setting End-of-Travel
Limit Switches.