Set Up and Calibration Procedures
Read Status Set Up Group
Revision 7
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
55
7/08
Read Status Set Up Group
Table 20 lists the parameters and selections available for the READ STATUS group.
Table 20 Read Status Set Up Group Parameters
Actuator Lower
Display
Prompt
Selections or
Range of Setting
Parameter Definition/PDA HercuLink
®
Prompt
FAILSF
NO
YES
FAILSAFE
—
Read Only.
Shows whether actuator in
failsafe.
No
— Actuator not in failsafe.
Yes
— Actuator in failsafe, see
Troubleshooting (page 105)
RAMTST
PASS
FAIL
RAM TEST DIAGNOSTIC
—
Read Only.
Shows status of
RAM test diagnostic.
Pass
— Test passed, no errors
Fail
— Test failed, see see
Troubleshooting (page 105)
SEETST
PASS
FAIL
SERIAL EEPROM TEST DIAGNOSTIC
—
Read Only.
Shows status of serial electrically eraseable PROM test
diagnostic.
Pass
— Test passed, no errors
Fail
— Test failed, see
Troubleshooting (page 105)
CFGTST
PASS
FAIL
CONFIGURATION TEST DIAGNOSTIC
—
Read Only.
Shows status of Configuration test diagnostic.
Pass
— Test passed, no errors
Fail
— Test failed, see
Troubleshooting (page 105)
CALTST
PASS
FAIL
CALIBRATION TEST DIAGNOSTIC
—
Read Only.
Shows
status of Calibration test diagnostic.
Pass
— Test passed, no errors
Fail
— Test failed, see
Troubleshooting (page 105)