Outlet pressure area p
d
range
[bar]
Weight
[kg]
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
F
[mm]
0.3
–
1
Approx. 6.0
195
40
29
101
26
127
0.5
–
40
Approx. 5.0
195
40
27
101
26
127
10
–
90
Approx. 6.5
315
40
27
101
26
127
Outlet pressure area p
d
range
[bar]
G
[mm]
H
[mm]
I
[mm]
J
[mm]
K
[mm]
L
[mm]
M
[mm]
N
[mm]
O
[mm]
0.3
–
1
215
93
67
56
88
230
132
90
24
0.5
–
40
191
36
67
56
68
209
156
-
-
10
–
90
191
36
67
32
75
202
132
-
-
Imperial system:
Outlet pressure area p
d
range
[bar]
Weight
[lbs]
A
[in]
B
[in]
C
[in]
D
[in]
E
[in]
F
[in]
0.3
–
1
Approx. 13.5
7.7
1.6
1.2
4.0
1.0
5.0
0.5
–
40
Approx. 11.0
7.7
1.6
1.1
4.0
1.0
5.0
10
–
90
Approx. 14.5
12.4
1.6
1.1
4.0
1.0
5.0
Outlet pressure area p
d
range
[bar]
G
[in]
H
[in]
I
[in]
J
[in]
K
[in]
L
[in]
M
[in]
N
[in]
O
[in]
0.3
–
1
8.5
3.7
2.6
2.2
3.5
9.1
5.2
3.5
0.9
0.5
–
40
7.5
1.4
2.6
2.2
2.7
8.2
6.1
-
-
10
–
90
7.5
1.4
2.6
1.3
3.0
8.0
5.2
-
-
Specific set range W
ds
Pilot spring
No.
Color
Wire diameter [mm]
Control stage
0.3
–
1 bar
(4.4
–
14.5 psi)
0
black
4.5
0.5
–
2 bar
(7.3
–
29 psi)
1
blue
3.6
1
–
5 bar
(14.5
–
72.5 psi)
2
black
4.5
2
–
10 bar
(29
–
145 psi)
3
grey
5
5
–
20 bar
(72.5
–
290 psi)
4
brown
6.3
10
–
40 bar
(145
–
580 psi)
5
red
7.0
10
–
50 bar
(145
–
725 psi)
6
Green
8/7
Pilot springs