CLSS Gateway - Installation and Users’ Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
100
BACnet Feature Activation
The BACnet Feature
Mode
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
0
IsmOff
Power-Up State
11
IsmEnabled
Set if point has been disabled and
subsequently enabled since startup.
12
IsmDisabled
Fire Device or Zone Disabled, Non-Fire
Device Disabled
Silence State
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
0
ssUnsilenced
Audibles Unsilenced
1
ssAudiblesSile
nced
Audibles Silenced
Operation
Expected
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
0
NA
Maintenance
Expected
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
NA
NA
NA
Event Enable
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
toOffNormal
toFault
Direct Reading
REAL
NA
% Alarm
Status Flags
Boolean
BACnet Status
Flags
NFN State
0,0,0,0
Normal
1,0,0,0
InAlarm
Fire Alarm, Security Alarm (Life/Property),
Critical Process Alarm (Life/Property),
Medical Emergency
1,1,0,0
InAlarm, Fault
Security Trouble, Fire Trouble, Non-Fire
Trouble, PreAlarm
1,0,0,1
InAlarm,
OutOfService
Fire Device or Zone Disabled, Non-Fire
Device Disabled
Out of Service
Boolean
NFN State
0
FALSE
All statuses other than disable
1
TRUE
Fire Device or Zone Disabled, Non-Fire
Device Disabled