CLSS Gateway - Installation and Users’ Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
103
Appendix A: Gateway Operating Conditions
Table A.1: Operational Requirements
A.1 Wirings and Power
Power Requirements
Working voltage range
18V - 30V DC
Current
For HON-CGW-DACT: 180mA (maximum)
For HON-CGW-MBB: 140mA (maximum)
NOTE
: The power requirement varies with the number of
interfaces used.
Location Requirements
Room Temperature
15 - 27° C (60 - 80° F)
Operational Temperature
0°C - 49°C (32°F - 120°F)
Relative humidity
93% + 2% RH (Non-condensing) at 32°C + 2°C (90° F + 3°F)
!
CAUTION:THE USEFUL LIFE OF THE SYSTEM'S STANDBY BATTERIES AND THE
ELECTRONIC COMPONENTS MAYBE ADVERSELY AFFECTED BY EXTREME
TEMPERATURE RANGES AND HUMIDITY. THEREFORE, IT IS RECOMMENDED THAT
THIS SYSTEM AND ITS PERIPHERALS BE INSTALLED IN AN ENVIRONMENT WITH A
NORMAL ROOM TEMPERATURE OF 15 - 27° C (60 - 80° F).
POWER LIMITED
NON-POWER LIMITED
J5
J4
POTS 2
POTS 1