CLSS Gateway - Installation and Users’ Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
123
FireWarden Panels
Connecting to the Panels
C.6.5 To Use Panel’s Printer Port Connection
Some FireWarden panels support data transfer through their printer terminal.
1. On the Gateway Side
• Connect the serial cable into the RS-232 port of the gateway.
The RS-232 port is labeled as 6 in the
2. On the Panel Side
Connect the serial cable in the DB9 serial port of the ANN-S/PG module on the panel.
3. Power Connection
On the Gateway Side
• Connect to the 24V DC external power supply.
• Switch the S7 Switch next to the RS-232 port towards
NUP_OUT
.
Figure C.12: The S7 Switch
On the Panel Side
Connect the power cable to a 24V DC external power source or the panel’s power
supply.
NOTE:
Compatible CLSS Gateway firmware versions: 2.1.11.16 and above
!
CAUTION: ENSURE THAT ONLY THE ANN-S/PG IS CONNECTED AND NOT THE CLSS GATEWAY. ONLY
ONE OF THESE TWO CAN BE CONNECTED. BOTH OF THEM MUST NOT BE CONNECTED TOGETHER.