CLSS Gateway - Installation and Users’ Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
125
Gamewell-FCI Panels
Connecting to the Panels
C.7 Gamewell-FCI Panels
C.7.1 Connection Options
Each variant of the Gamewell-FCI panel offers various connection options.
The gateway operates only with the Gamewell-FCI fire alarm control panels listed in the
table below:
Table C.5: Gamewell-FCI Panel Connection Options
Minimum Required Versions
Gamewell-E3: 7.00.106
Gamewell-S3: 7.00.106
CLSS Gateway: 3.1.4.72
LCD-SLP (Display Panel): 2.12.090
NGA-K: 7.00.100
Limitation(s)
Support for CAM-event alerts is
currently
not available for the
CLSS Gateway
. When the
support is available, the
CLSS Gateway
will send these messages to
CLSS Site Manager
(Cloud) and the
CLSS
App.
C.7.2 To Use Panel’s Printer Port Connection
Gamewell panels support data transfer through their RS-485 connection. The transferred
data is stored in the
CLSS Site Manager
.
1. On the Gateway Side
1. Connect the + (24 V) wire to the IN+ pin of an RS-485 port.
2. Connect the - (GND) wire to the IN- pin of an RS-485 port.
The RS-485 ports are labeled as 3 and 4 in the
2. On the Panel Side
•
•
•
E3 Series Panel
At the TB3 terminal of the panel,
• Connect the +ve wire to the TB3-1 pin.
• Connect the -ve wire to the TB3-2 pin.
At the TB6 terminal of the panel,
• Connect the GND wire to the TB6-1 pin.
• Connect the TxD wire to the TB6-2 pin.
• Connect the SUPV wire to the TB6-3 pin.
Fire Alarm Panel Models
RS-485
UART/TTL
RS-232
USB
Ethernet
E3 Series Panels
ILI-MB-E3
Yes
No
No
Yes
No
ILI-S-E3
No
No
No
Yes
No
ILI95-MB-E3
Yes
No
No
Yes
No
ILI95-S-E3
No
No
No
Yes
No
S3 Series Panels
SLP-E3
Yes
No
No
Yes
Yes
INI-7100
Yes
No
No
Yes
No
!
CAUTION: DO NOT INSTALL DACT-E3 AND THE CLSS GATEWAY TOGETHER ON AN ILI-MB-E3 CIRCUIT
BOARD OR AN ILI95-MB-E3 CIRCUIT BOARD. YOU CAN USE DACT-E3 ON A DIFFERENT NODE WITHIN
THE NETWORK.