Gent Panels
Connecting to the Panels
C.8.3 Vigilon Series Panels
For a fixed gateway, we recommend using a UART/TTL connection. If it is not available,
use a RS-232 connection.
To Use a UART/TTL Connection
1. On the Gateway Side
Connect the male UART/TTL cable to the Rx (Red), Gnd (Silver), and Tx (White) UART/TTL
terminals of the gateway.
The UART/TTL port is labeled as 5 in
2. On the Panel Side
1. Within the panel, find the backplane PCB board (see
.
2. Connect the 3.5mm phono socket to the P11 connector on the panel’s PCB.
Figure C.19: Vigilon Panels: UART/TTL Connection
3. Power Connection
On the Gateway Side
Connect the power cable to a 24V DC external power source.
To Use an RS-232 Port via an I/O Card
Using an add-on I/O card (VIG-IOC-DOM), certain Vigilon panel variants can
communicate with the CLSS Gateway.
•
The I/O card has a rotary switch, which should point to 5.
•
The baud rate of the I/O card should be 19200.
NOTE:
The external power supply must be dedicated and not shared with any other
devices.
NOTE:
The panel’s power supply to the gateway must be 24V DC power.