Section 4: Installation
You can use a fixed gateway in the fire detection system.
4.1 Wall Mounting the Fixed Gateway
It is recommended to keep the gateway within 1 meter (3-feet) from the connected panel
or the network card. The minimum distance between the gateway and the panel should
be 30 cm.
Follow the instructions below to mount the gateway enclosure:
1. Open the package and take out the contents.
2. Inspect the contents for damage. If there is any damage, do not proceed with
installation. Return the package.
3. Place the right-side door edge on a flat surface for support.
4. At the right-side door edge, punch out a hole for the door locking screw or for an
optional keyed lock (see
).
Figure 4.1: Screw Hole Knock Out
5. Depending upon the wall construction, select suitable screws to mount the enclosure.
6. Place the backbox on the wall where the enclosure is to be mounted.
7. Confirm that the placement of the backbox allows the door to swing open freely.
NOTE:
This section refers to the fixed gateway P/N: HON-CGW-MBB. For instructions on
mounting the portable gateway, P/N: CGW-MB, refer to the NBB-2 installation document
LS10250-000NF-E.
!
CAUTION: THE GATEWAY MUST BE INSTALLED INDOORS IN A DRY LOCATION.
WARNING: INSTALL AS PER THE LOCAL BUILDING AS WELL AS CUSTOMER-SPECIFIC REQUIREMENTS. FOR
EXAMPLE, INSTALLING AND OPERATING THE GATEWAY WITH ITS WIRELESS TECHNOLOGY MIGHT BE
RESTRICTED NEAR MEDICAL EQUIPMENT, FUELS, OR CHEMICALS. ENSURE THAT THERE ARE NO CONFLICTS.
!
CAUTION: THE EQUIPMENT IS SUITABLE FOR MOUNTING AT A MAXIMUM HEIGHT OF 9.9 FEET ONLY.
NOTE:
In a low LTE signal area, you may choose to use external aerials.