CLSS Gateway - Installation and Users’ Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
53
Installation and Configurations
Modbus Communications
7.14 Installation and Configurations
The CLSS Gateway can communicate with the Modbus client in an Ethernet LAN.
7.15 The IP Settings
The following information applies to IP settings:
•
You can use only the
eth1
port for connections to Modbus clients. For more details,
refer to
7.17 "To Configure the Modbus Settings"
.
•
Each CLSS Gateway is shipped with a default node number of 235.
•
The computer used to configure the CLSS Gateway must establish an IP connection
to the gateway. Consult with a network administrator if unsure how to make this
connection.
•
Connecting more than one CLSS Gateway prior to reconfiguring the IP address will
result in an IP address conflict.
7.16 To Connect with the Modbus Client
1. At the CLSS Gateway side, connect an Ethernet cable to the Ethernet Port 1.
2. At the Modbus client side, connect the other end of the Ethernet cable to the system
running the Modbus client.
Fire Alarm Panel
CLSS
Cloud
Modbus
Client
Configuration
Computer
Mobile
Connection
/NUP
Ethernet
Connection
WHITE COLOR
GREEN COLOR
RED COLOR
BLACK COLOR
BROWN COLOR
P7
P2
P4
J5
P1
Future Use
Future Use
Future Use
(
Eth 1
)
(
Eth 0
)