To Configure the Modbus Settings
Modbus Communications
13.Click
SAVE
.
14.Press the S6 button again until the LED indicator DL3 changes from ON to flashing.
Node Unit ID
Displays the unit ID that each node uses on the Modbus network.
If for any reason the node unit ID needs to be changed, click the value and enter
the new Modbus network unit ID number (1-240). Since each unit ID in the
Modbus network needs to be unique, change this number only if there is a
conflict between unit IDs in the Modbus network.
If a unit ID number is changed to a number already assigned to another node,
the node currently having that unit ID number swaps the unit ID number with
the node that was changed.
Example: The node assigned Unit ID #214 is changed to be Unit ID #5. The
result is that the node that was Unit ID #214 is now #5 and the node that was
Unit ID #5 is now #214.
However, the CLSS Gateway configuration web page does accept a new unit ID
number that is currently being used by a monitored node. In order to reassign a
unit ID number used by a monitored node, first assign a new unit ID number for
the monitored node.
Notes
:
The
Unknown
nodes can only be seen in the
Show All Nodes
mode.
If an
Unknown
node comes on line and is found to be of the wrong type for the
CLSS Gateway to monitor, its Monitored field is automatically set to
No
.
Some nodes in the node list are not usable by the CLSS Gateway and therefore
are not configurable and do not have a unit ID.
Monitoring
• Select
Yes
to monitor the node.
• Select
No
if the node is not to be monitored.
At a given time, up to 10 nodes* can be monitored.
* Excluding the CLSS Gateway.
MODBUS TOOLS
Control Functionality
1. Go to
Modbus Tools
in
Modbus Settings
.
2. Enable or disable as needed in the control functionality.
3. Read the UL Void message shown, if enabled.
4. Click
Save
to save it.
5. Wait until the CLSS Gateway shows the changes.
CSV REPORTS DOWNLOAD
Actual Points
Click
Download
to download details of points (detectors and modules), which
the panel monitors. The downloaded details will be in the CSV format.
All Points
Click
Download
to download details of monitored and unmonitored points. The
downloaded details will be in the CSV format.
CONNECTED CLIENTS
Show Connected
Clients
Click
Show
to view all the clients connected to the Modbus master application.
Table 7.4: Settings for Modbus Client Communications (Continued)
Field
Description
NOTE:
The configuration changes are enabled only after the gateway changes from the
configuration mode to operational mode.