BACnet Feature Activation
The BACnet Feature
8.6.4 Standard Object Types Supported—Multi-State Input Standard Object
Types
Silence State
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
0
ssUnsilenced
Audibles Unsilenced
1
ssAudiblesSile
nced
Audibles Silenced
Operation
Expected
BACnet
Enumeration
NFN State
0
NA
Maintenance
Expected
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
NA
NA
NA
Event Enable
BACnet Event
Transition Bit
toOffNormal
toFault
Direct Reading
REAL
NA
% Alarm
Status Flags
Boolean
BACnet Status
Flags
NFN State
0,0,0,0
Normal
1,0,0,0
InAlarm
Fire Alarm, Security Alarm (Life/Property),
Critical Process Alarm (Life/Property),
Medical Emergency
1,1,0,0
InAlarm, Fault
Security Trouble, Fire Trouble, Non-Fire
Trouble, PreAlarm
1,0,0,1
InAlarm,
OutOfService
Fire Device or Zone Disabled, Non-Fire
Device Disabled
Out of Service
Boolean
NFN State
0
FALSE
All statuses other than disable
1
TRUE
Fire Device or Zone Disabled, Non-Fire
Device Disabled
Present Value
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
1
None
Normal
2
None
All statuses other than those included in
3 and 4 below.
3
None
Security Trouble, Fire Trouble, Non-Fire
Trouble
4
None
Fire Device or Zone Disabled, Non-Fire
Device Disabled