CLSS Gateway - Installation and Users’ Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
96
BACnet Feature Activation
The BACnet Feature
8.6.3 Standard Object Types Supported—Life Safety Point/Life Safety Zone
Present
Value
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
0
IssQuiet
Normal
1
IssPreAlarm
PreAlarm
2
IssAlarm
Fire Alarm, Security Alarm (Life/Property),
Critical Process Alarm, (Life/Property), Medical
Emergency
3
IssFault
Security Trouble, Fire Trouble, Non-Fire Trouble,
Fire Device or Zone, Disabled, Non-Fire Device
Disabled
7
IssActive
Non-Fire Activation
22
IssSupervisory
Supervisory (Equipment), Supervisory (Guard's
Tour)
Tracking
Value
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
0
IssQuiet
Normal
1
IssPreAlarm
PreAlarm
2
IssAlarm
Fire Alarm, Security Alarm (Life/Property),
Critical Process Alarm (Life/Property), Medical
Emergency
3
IssFault
Security Trouble, Fire Trouble, Non-Fire Trouble,
Fire Device or Zone, Disabled, Non-Fire Device
Disabled
7
IssActive
Non-Fire Activation
22
IssSupervisory
Supervisory (Equipment), Supervisory (Guard's
Tour)
Event State
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
0
EsNormal
Normal
1
EsFault
Security Trouble, Fire Trouble, Non-Fire Trouble,
Fireevice Disabled, Non-Fire Device Disabled
2
EsOffNormal
All statuses other than normal and fault.
Reliability
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
0
reNoFaultDetected
All statuses other than trouble.
7
re_UnreliableOther
Security Trouble, Fire Trouble, Non-Fire Trouble
Mode
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
0
IsmOff
Power-Up State
11
IsmEnabled
Set if point has been disabled and subsequently
enabled since startup.
12
IsmDisabled
Fire Device or Zone Disabled, Non-Fire Device
Disabled