Maintenance
User manual for HON R100 gas pressure regulator with HON P095NG pilot
60
Figure
Step
Description
39
Put the dome back in place. Tighten the
nuts
(1) in a criss‐cross sequence.
Observe the tightening torque information
provided in the table before this section.
Proceed as follows:
Figure
Step
Description
1
Replace the O‐ring (1) in the body hole
intended for the position indicator with a
new, greased O‐ring.
2
Insert the inner pin, including the spring
(1), back into the hole (2) for the position
indicator.
3
Use an open‐end wrench to screw the
position indicator’s housing (1) back in
place.
4
Pull the magnetic ring (1) over the position
indicator’s housing. The magnetic ring
position shown in the figure to the left
shows the correct installation height.
Maintaining and in‐
stalling the position
indicator