HPSR10*

5

33-00331EF—05

Boiler Controls

Honeywell Hydronic Panels are capable of managing boilers with DHW priority. The panel features two isolated end 
switches labeled Boiler and End Switch for TT outputs to the boiler. Two slide switches are available to provide simple 
programing of the end switches to meet the desired application. See the operational matrix below detailing functionality 
of the switches.

Additionally, this panel features a LOW LIMIT input which must be closed for pumps to be activated. This input comes 
with a factory installed jumper for cold start boiler operation when the controlling Aquastat has a HIGH LIMIT only. If the 
installed boiler requires warm up time then this jumper should be removed and wired to the boiler.

Fig. 11. 

Fig. 12. 

Fig. 13. 

T-STAT

CALL

STATUS OF

ZR/ZC

CLOSED

BOILER RELAY=ON

END SWITCH=ON

ZONE PUMP=OFF

OPEN

NO PRIORITY ZONE OR PRIORITY END SWITCH

BOILER RELAY=ON

END SWITCH=ON

ZONE PUMP=ON

M37144

T-STAT

CALL 

STATUS OF

ZR/ZC

OPEN

BOILER RELAY = ON

END SWITCH = ON

ZONE PUMP = ON

IS THIS THE

PRIORITY ZONE? 

DEACTIVATE ALL

OTHER ZONES 

YES

IS PRIORITY

ACTIVE? 

NO

NO

WAIT FOR

PRIORITY ZONE

TO SATISFY  

YES

CLOSED

PRIORITY ZONE, NO PRIORITY END SWITCH

M37145

BOILER RELAY = ON

END SWITCH = ON

ZONE PUMP = OFF

M37146

T-STAT

CALL

STATUS OF

ZR/ZC

CLOSED

BOILER RELAY = ON

END SWITCH = ON

ZONE PUMP = ON

IS THIS THE

PRIORITY ZONE? 

DEACTIVATE ALL

OTHER ZONES 

YES

IS PRIORITY

ACTIVE? 

NO

NO

WAIT FOR

PRIORITY ZONE  

TO SATISFY

YES

STATUS OF

ZR/ZC

CLOSED

OPEN

OPEN

PRIORITY ZONE, PRIORITY END SWITCH

BOILER RELAY = ON

END SWITCH = ON

ZONE PUMP = OFF

BOILER RELAY = ON

END SWITCH = OFF

ZONE PUMP = ON

BOILER RELAY = ON

END SWITCH = OFF

ZONE PUMP = OFF

Summary of Contents for HPSR103

Page 1: ...y professionals only PANEL SPECIFICATIONS Table 1 NOTES All circulator relay connections including ZC ZR are rated for 5A full load and 30A locked rotor 1 6 to 1 2HP depending on technology at 120VAC Check circulator plate ratings to ensure full load current is not exceeded End switch connections are rated 24V 1 Amp All thermostat connections supply a 24V Class 2 output Model Zones Transformers In...

Page 2: ... screws in Fig 3 Din Rail Flow 1 Mount the DIN rail as per manufacturers instruc tions Fig 4 2 Hang panel by the tabs on the rail s top edge Fig 5 3 Snap into rail by pressing the bottom of panel against the wall Fig 6 4 To remove lift up on panel and pull the top away from the wall Fig 7 M37083 M37084 M37085 M37086 M37087 M37088 M37089 ...

Page 3: ...V power to electronic thermostats NOTE It is up to the installer to ensure that the 40VA per transformer limit is not exceeded Additionally Honeywell Hydronic Panels are compatible with Honeywell Equipment Interface Modules in installations were sufficient wiring is not available Fig 8 NOTE For power stealing thermostats wire to R and W on the zone panel There are no additional com ponents require...

Page 4: ... 6 Power Boiler End Switch HWSR506 6 ZONE PUMP CONTROLLER ZR ZC 2 AMP TRANSFORMER FUSE ZONE 1 FUSE ZONE 2 FUSE ZONE 3 FUSE ZONE 4 FUSE ZONE 5 FUSE PRIORITY END SWITCH PRIORITY END SWITCH PRIORITY ZONE ZONE 1 PRIORITY ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 GROUNDING BAR INCLUDED FOR GROUNDING THERMOSTAT WIRING CONNECTED THERMOSTAT WIRING NON CONNECTED OR POWER STEALING R W C R W C R W C R W C T T T T Z...

Page 5: ...ed and wired to the boiler Fig 11 Fig 12 Fig 13 T STAT CALL STATUS OF ZR ZC CLOSED BOILER RELAY ON END SWITCH ON ZONE PUMP OFF OPEN NO PRIORITY ZONE OR PRIORITY END SWITCH BOILER RELAY ON END SWITCH ON ZONE PUMP ON M37144 T STAT CALL STATUS OF ZR ZC OPEN BOILER RELAY ON END SWITCH ON ZONE PUMP ON IS THIS THE PRIORITY ZONE DEACTIVATE ALL OTHER ZONES YES IS PRIORITY ACTIVE NO NO WAIT FOR PRIORITY ZO...

Page 6: ...se harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Mylar cover Fig 15 Mylar cover 5 YEAR LIMITED WARRANTY Honeywell warrants this product to be free from defects in the workmanship or materials under normal use and service for a period of five 5 years from the date of purchase by the consumer If at any time duri...

Page 7: ...s professionnels seulement SPÉCIFICATIONS DU PANNEAU Tableau 1 REMARQUE Tous les raccordements du relais du circulateur y compris les ZC ZR sont adaptés à un rotor bloqué de 30 A et à une charge nominale de 5 A 1 6 à 1 2 HP en fonction de la technologie à 120 V c a Vérifiez les valeurs sur la plaque du circulateur afin de vous assurer que le courant nominal n est pas dépassé Les raccordements de l...

Page 8: ... Rail DIN 1 Montez le rail DIN conformément aux instructions du fabricant Fig 4 2 Suspendez le panneau par les languettes sur le bord supérieur du rail Fig 5 3 Emboîtez le panneau dans le rail en appuyant le bas du panneau contre le mur Fig 6 4 Pour retirer le panneau soulevez le et écartez la partie supérieure du mur Fig 7 M37083 M37084 M37085 M37086 M37087 M37088 M37089 ...

Page 9: ...oniques qui ont besoin de l alimentation REMARQUE il incombe à l installateur de veiller à ce que la limite de 40 VA par transformateur ne soit pas dépassée En outre les panneaux hydroniques Honeywell sont compatibles avec les modules d interface de l équipement Honeywell dans les installations ne disposant pas de suffisamment de câblage Fig 8 REMARQUE Pour les thermostats qui n ont pas besoin du ...

Page 10: ...SIBLE ZONE 1 FUSIBLE ZONE 2 FUSIBLE ZONE 3 FUSIBLE ZONE 4 FUSIBLE ZONE 5 INTERRUPTEUR D EXTRÉMITÉ PRIORITAIRE INTERRUPTEUR D EXTRÉMITÉ PRIORITAIRE ZONE PRIORITAIRE ZONE 1 PRIORITÉ ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 CÂBLE DE MISE À LA TERRE ET CONNECTEUR POUR LA MISE À LA TERRE INCLUS CÂBLAGE DU THERMOSTAT AVEC LE FIL C CÂBLAGE DU THERMOSTAT SANS LE FIL C MARCHE ARRÊT MARCHE ARRÊT 24 V c a DU TRANS...

Page 11: ...S DE LA CHAUDIÈRE MARCHE INTERRUPTEUR D EXTRÉMITÉ MARCHE POMPE DE LA ZONE MARCHE OUVERT RELAIS DE LA CHAUDIÈRE MARCHE INTERRUPTEUR D EXTRÉMITÉ MARCHE POMPE DE LA ZONE ARRÊT MF37144 ZONE PRIORITAIRE AUCUN INTERRUPTEUR D EXTRÉMITÉ PRIORITAIRE DEMANDE DU THERMOSTAT STATUT DE ZR ZC OUVERT RELAIS DE LA CHAUDIÈRE MARCHE INTERRUPTEUR D EXTRÉMITÉ MARCHE POMPE DE LA ZONE MARCHE EST CE UNE ZONE PRIORITAIRE ...

Page 12: ...en mylar Fig 15 Couvercle en mylar GARANTIE LIMITÉE DE 5 ANS Honeywell garantit ce produit contre tout vice de fabrication ou de matériau dans la mesure où il en est fait une utilisation et un entretien convenables et ce pour cinq 5 ans à partir de la date d achat par le consommateur En cas de défaillance ou de mauvais fonctionnement pendant la période de garantie Honeywell remplacera ou réparera ...

Reviews: