background image

7

Securing the radiator controller

i

The radiator controller and the batteries can be 
secured against removal by using the supplied 
screws.

Setting the position of the display

In order to improve the legibility the display of the 
radiator controller can be tilted to different positions 
(10°, 20°, 30°, 40°). 
The angle of 40° can be fixed with the supplied display 
support.

1.

2.

Mounting

1. Lift the display and set it to the desired angle.
2. If desired, tilt the display by 40° and slide the display 

support from above between the display and the 
housing until it latches in.

Unmounting

 

f

Press the display support in at the back and remove 
it upwards.

Connecting an external window contact

The floating external window contacts HCA30 can be 
connected to the HR92 radiator controller.

i

The cable ACS90 is required to connect the external 
window contact.

• 

Micro B mini-plug / open ends 

• 

2 m long

• 

Not included in the scope of delivery

Operation with window contact

When the window is opened, the window contact is 
opened and the radiator valve closes. When the window 
is closed again, the radiator controller returns to normal 
operation. 
The frost-protection function ensures that the radiator 
valve opens when the tempera
ture drops below 5 °C.

i

If a cabled window contact is removed, Parameter 11 
has to be modified to 0 or 1, see Section 5.

Cable connection

 

f

Connect cable ACS90 as follows to the window 
contact HCA30:

white 

green 

black GND

ACS90

Connecting the cable to the radiator controller 
HR92

2.

1.

1. Remove the side cover from the radiator controller.
2. Insert the cable ACS90 into the radiator controller 

HR92.

The radiator controller recognises the connected 
window contact automatically.

Summary of Contents for HR92

Page 1: ...s are available as accessories An external window contact can be connected optionally Energy saving features With the window function the radiator valve is closed when ventilating the room If an external window contact is used the radiator valve is closed when a window is open CAUTION f f Use the radiator controller only in accordance with these operating instructions f f Do not let children play ...

Page 2: ...tteries are dead and have to be replaced Radio signal display Display Meaning signal 05 Field strength excellent signal 03 Field strength good signal 01 Field strength weak 4 Mounting Ready to operate in three steps Insert batteries and set language Establish radio connection Mount on radiator controller FINISHED Inserting changing batteries The radiator controller is set for the following battery...

Page 3: ...ries or throw them into fire f f Dispose of used batteries ecologically Establishing radio connection The radiator controller HR92 communicates with the central operating device by radio using the frequency of 868 MHz To this purpose the connection between the HR92 and the central operating device has to be established first This process is called BINDING In the case of preconfigured devices bindi...

Page 4: ...ounting location for the room unit and repeat binding Clearing binding at the HR92 1 Press the button briefly 2 Hold the button pressed for 5 seconds 3 Select bind using the adjustment dial and keep the button pressed until cleared is displayed Binding is deactivated Radio test 1 Press the button briefly 2 Hold the button pressed for 5 seconds 3 Select rf check using the adjustment dial and confir...

Page 5: ... and moisture f f Mount the radiator controller indoors only f f Protect the radiator controller against humidity moisture dust direct sunlight or exposure to excessive heat Removing the old thermostat head 1 2 1 Turn the old thermostat head counter clockwise until it stops and loosen the mounting ring 2 Remove the old thermostat head from the radiator valve Selecting the adapter The radiator cont...

Page 6: ...radiator controller is in the open position 2 Put the radiator controller onto the valve baseplate so that the indentation latches in and is no longer visible 3 Lock the radiator controller in the end position To do so push the slide towards After approx 1 minute cycl self test is displayed Afterwards the radiator controller changes to normal operation 25 2 C i The radiator controller only operate...

Page 7: ...the HR92 radiator controller i The cable ACS90 is required to connect the external window contact Micro B mini plug open ends 2 m long Not included in the scope of delivery Operation with window contact When the window is opened the window contact is opened and the radiator valve closes When the window is closed again the radiator controller returns to normal operation The frost protection functio...

Page 8: ... controller and in the room Factory setting 0 Par Set ting Meaning 9 0 1 2 Battery type Alkaline Lithium NiMH accumulator chargeable 10 0 1 Display of the valve position No display of the valve position Momentary display of the valve position 11 0 1 2 Window open function Off no window function Auto corresponding to Parameters 3 5 Cabled with floating window contact 12 0 1 Restore to factory setti...

Page 9: ...red at another point in the room Parameter 8 Temperature offset Since the radiator controller measures the room temperature in the area of the radiator it is possible that this temperature deviates from the temperature measured at a different point in the room If for example 20 C is measured in the room and 21 0 C at the radiator this effect can be compensated by an offset of 1 0 C Parameter 10 Di...

Page 10: ...ing system from freezing up frost is displayed i The heating must be switched on to ensure the frost protection function 7 Help with problems Error table Problem Display Cause Remedy flashing Batteries flat Replace the batteries icons are flashing No radio com munication Check the radio connection between the HR92 and the central operating device radio test Repeat the binding procedure Check the p...

Page 11: ...ation ISM 868 0 870 0 MHz RX Class 2 Range typically 30 m within residential buildings Supply voltage Battery type LR6 AA AM3 Alkaline 2 x 1 5 V Lithium 2 x 1 5 V NiMH 2 x 1 2 V Connection to the radiator M30 x 1 5 Ambient temperature 0 50 C Dimensions 96 x 54 x 60 mm Ambient conditions For living area business and commercial areas as well as small businesses Humidity 10 90 rel humidity 9 Disposal...

Page 12: ...horized Representative 11 Binding and radio test Overview Press the button briefly Display Room information Hold the button pressed for 5 seconds bind rf check exit button Hold the button pressed until button button binding cleared checking flashes back to standard display success button Radio signal from operating device back to standard display Display of the field strength exit button back to s...

Page 13: ...ut our full range of Heating Products Central Heating Controls Honeywell Heating Controls Danfoss Heating Controls Radiator Valves Fernox Sentinel Magnaclean Warmup underfloor heating Water Heaters Hand Dryers ...

Reviews: