Gas pressure regulator with incorporated filter 

EN1C-0003NL05 R

1

2

05

 

1

HUPF Series 

HUPF Series 

GAS PRESSURE REGULATOR WITH 

INCORPORATED FILTER 

INSTRUCTION SHEET

 

DESCRIPTION 

 

Spring-loaded regulator with inlet pressure compensation 

and zero shut-off. 

The outlet pressure is kept constant with changing gas flow 

as  a  function  of  the  spring  setting.  The  zero  shut-off  prevents  the 

outlet  pressure  from  increasing  when  there  is  no  gas  flow  through 

the regulator. 

 

APPLICATION 

 

To  regulate  gas  and  air  inlet  pressure  for  gas  burners,  including 

mixed and combined systems and in industrial distribution systems. 

Applicable types of fuel: 

 manufactured gases (town gas) 

 

natural gases (group H - methane) 

 

liquefied petroleum gas (LPG) 

 

non-aggressive gases 

 

air 

The gas pressure regulators comply with the requirements of 

EN88

-1

, class B, group 2. 

These gas pressure regulators are available in two versions; 

with or without incorporated filter, see product range page 2. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for HUPF Series

Page 1: ...ts the outlet pressure from increasing when there is no gas flow through the regulator APPLICATION To regulate gas and air inlet pressure for gas burners including mixed and combined systems and in industrial distribution systems Applicable types of fuel manufactured gases town gas natural gases group H methane liquefied petroleum gas LPG non aggressive gases air The gas pressure regulators comply...

Page 2: ... i e zero shut off Torsion and bending stress Pipe connections meet group 2 according to EN 88 1 requirements Set point accuracy According to EN88 1 class A group 2 Adjustment spring range Max allowed pressure Up to 1 bar without body damages Ambient temperature range 15 C 60 C Material of pressure receiving parts Elastomer EN549 Sealing elements Hydrocarbon resistant NBR rubber type NBR 70 Safety...

Page 3: ...he same direction as the arrow on the housing of the gas regulator Use a sound taper fitting with thread according to ISO 7 1 BS21 DIN 2999 or a piece of new properly reamed pipe free from swarf Do not thread or tighten the pipe or pipe fitting too far Otherwise regulator distortion and malfunction could result Apply a moderate amount of good quality thread compound to the pipe or fitting only lea...

Page 4: ...l Connection inch mbar A B C D E F HUPF015B110 1 2 500 138 1 2 175 HUPF020B110 3 4 500 134 3 4 175 HUPF025B110 1 500 134 1 175 HUPF032B110 1 1 4 500 194 1 1 4 255 HUPF040B110 1 1 2 500 194 1 1 2 255 HUPF050B110 2 500 236 2 316 HUPF050B310 DN50 500 352 DN50 349 HUPF065B310 DN65 500 350 DN65 427 HUPF080B310 DN80 500 350 DN80 434 HUPF100B310 DN100 500 415 DN100 502 ...

Page 5: ...he required outlet pressure by proceeding with step 1 to 4 of Outlet pressure adjustment section on this page Final checkout of the installation Set the appliance in operation after any adjustment and observe several complete cycles to ensure that all burner components function correctly MAINTENANCE The regulators are completely maintenance free In the event of a breakdown a general overhaul and f...

Page 6: ... 1000 Nominal flow rate m3 h Pressure drop mbar 1 2 3 4 1 1 1 4 1 1 2 2 DN65 DN80 DN100 Honeywell Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Sàrl 1180 Rolle Z A Lá Piece 16 Switzerland by its Authorized Representative Automation and Control Solutions Combustion Controls Europe Honeywell BV Phileas Foggstraat 7 7821 AJ Emmen The Netherlands Tel...