background image

Gas pressure regulator with incorporated filter 

EN1C-0003NL05 R

1205

 

2

HUPF Series 

SPECIFICATION 

 

Product range 

Model 

HUPF 

(pipe sizes 1/2“ up to DN 100) 

with 

filter. 

 

Dimensions 

See dimensional drawing and table on page 4. 

 

Pipe size 

1/2“ up to 2“ inlet and outlet internal pipe thread according 

ISO 7-1. 

DN40,  DN50,  DN65,  DN80  and  DN100  inlet  and  outlet 

flange connections according to ISO 7005 EN 1092-4 

 

Connections 

Inlet pressure tap connections. 

 

Capacity 

See Capacity curves HUPF Series on page 6. 

 

Maximum working pressure 

500 mbar 

NOTE: minimum inlet pressure range: 

desired outlet pr2.5 mbar up to 

5

00 mbar. 

 

Outlet pressure range 

5 to 300 mbar 

The  appropriate  outlet  pressure  range  is  obtained by the 

use of different springs. 

NOTE: The regulators are supplied standard with a white 

spring - see „Spring setting range“ below 

 

Closing pressure 

Conform EN 88

-1

 specification (i.e. zero shut-off) 

 

Torsion and bending stress 

Pipe connections meet group 2, according to EN 88

-1

 

requirements. 

 

Set point accuracy 

According to EN88-1, class A group 2. 

 

 

 

 

Adjustment spring range 

 

 

Max. allowed pressure 

Up to 1 bar without body damages 

 

Ambient temperature range 

-15 °C....+60 °C 

 

Material of pressure receiving parts 

Elastomer EN549 

 

Sealing elements 

Hydrocarbon resistant NBR rubber type NBR 70 

 

Safety diaphragm 

An external breather/outlet pipe is not necessary as the 

incorporated  safety  diaphragm  ensures  that,  in  the  event 

of 

breakage of the operating diaphragm. No gas leakage into 

the environment of over 30dm3/h is possible. The above in 

compliance with para. 3.3.2. of UNI EN 88 specification. 

 

Body material 

Aluminium alloy die cast EN AB 46100, EN AB43100 

 

Internal parts 

AISI 304/Delrin 

 

Filter 

HUPF Series only. 

Filter element Synthetic fiber DVGW G260/1 

 

Filtering grade 

= 50µ 

 

Standard and Approvals 

The  HUPF  Series  gas  pressure  regulator  with 

and without incorporated filter conform to the following 

EC-directives: 

• Gas Appliance Directive (90/396/EEC)  

 PIN: 0063AR4719

 

 

 

 

Summary of Contents for HUPF Series

Page 1: ...ts the outlet pressure from increasing when there is no gas flow through the regulator APPLICATION To regulate gas and air inlet pressure for gas burners including mixed and combined systems and in industrial distribution systems Applicable types of fuel manufactured gases town gas natural gases group H methane liquefied petroleum gas LPG non aggressive gases air The gas pressure regulators comply...

Page 2: ... i e zero shut off Torsion and bending stress Pipe connections meet group 2 according to EN 88 1 requirements Set point accuracy According to EN88 1 class A group 2 Adjustment spring range Max allowed pressure Up to 1 bar without body damages Ambient temperature range 15 C 60 C Material of pressure receiving parts Elastomer EN549 Sealing elements Hydrocarbon resistant NBR rubber type NBR 70 Safety...

Page 3: ...he same direction as the arrow on the housing of the gas regulator Use a sound taper fitting with thread according to ISO 7 1 BS21 DIN 2999 or a piece of new properly reamed pipe free from swarf Do not thread or tighten the pipe or pipe fitting too far Otherwise regulator distortion and malfunction could result Apply a moderate amount of good quality thread compound to the pipe or fitting only lea...

Page 4: ...l Connection inch mbar A B C D E F HUPF015B110 1 2 500 138 1 2 175 HUPF020B110 3 4 500 134 3 4 175 HUPF025B110 1 500 134 1 175 HUPF032B110 1 1 4 500 194 1 1 4 255 HUPF040B110 1 1 2 500 194 1 1 2 255 HUPF050B110 2 500 236 2 316 HUPF050B310 DN50 500 352 DN50 349 HUPF065B310 DN65 500 350 DN65 427 HUPF080B310 DN80 500 350 DN80 434 HUPF100B310 DN100 500 415 DN100 502 ...

Page 5: ...he required outlet pressure by proceeding with step 1 to 4 of Outlet pressure adjustment section on this page Final checkout of the installation Set the appliance in operation after any adjustment and observe several complete cycles to ensure that all burner components function correctly MAINTENANCE The regulators are completely maintenance free In the event of a breakdown a general overhaul and f...

Page 6: ... 1000 Nominal flow rate m3 h Pressure drop mbar 1 2 3 4 1 1 1 4 1 1 2 2 DN65 DN80 DN100 Honeywell Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Sàrl 1180 Rolle Z A Lá Piece 16 Switzerland by its Authorized Representative Automation and Control Solutions Combustion Controls Europe Honeywell BV Phileas Foggstraat 7 7821 AJ Emmen The Netherlands Tel...