PRODUCT DATA

31-00455-01

HUVF Series Duct Mounted 
UV System

APPLICATION

Honeywell HUVF Series is designed for installation inside 
the air handling units or ductwork of the HVAC system for 
the purpose of surface disinfection using ultraviolet 
germicidal irradiation. This system is uses UV-C 
technology which is effective in killing mold, bacteria and 
viruses. This system is effective in coil cleaning and helps 
in maintaining the cooling coil efficiency. This UV based 
system is effective in deactivating the microbes and 
improving the overall indoor air quality by reducing the 
microbial load on the indoor air.

FEATURES

• Suitable for mounting in AHU near Cooling coil.

• Plug and Play design enables ease of installation.

• Effective on all types of pathogens.

• HUVF58C2000 / HUVF58S2000: 2 Lamps - 23W max. 

each. 

• HUVF58C1000 / HUVF58S1000: 1 Lamp - 23W max.

• Effective in IAQ improvement.

• Effective deactivation of viruses and bacteria killing 

with 254 nm wavelength UVC.

• Effective in reducing microbe generated VOCs in 

AHU.

SPECIFICATIONS

Model:  

See Table 1.

Electrical Ratings: 

Power Consumption: See Table 1.
Voltage Rating: 230 Vac ±10%, 50/60 Hz

Operating Environment:

Temperature: 5 °C to 40 °C
Humidity: 0 to 90% RH (non-condensing)

Mounting:

Mounts into the AHU between the pre-filters and cooling 

coils with lamps facing the cooling coils.

Contents

Application .....................................................................................

1

Features ..........................................................................................

1

Specifications ...............................................................................

1

Planning the Installation .........................................................

3

Installation ....................................................................................

4

Wiring ..............................................................................................

5

Operation and Maintenance  ..................................................

5

Service .............................................................................................

6

Electrical Troubleshooting ......................................................

7

Parts List  ........................................................................................

7

Summary of Contents for HUVF Series

Page 1: ... AHU near Cooling coil Plug and Play design enables ease of installation Effective on all types of pathogens HUVF58C2000 HUVF58S2000 2 Lamps 23W max each HUVF58C1000 HUVF58S1000 1 Lamp 23W max Effective in IAQ improvement Effective deactivation of viruses and bacteria killing with 254 nm wavelength UVC Effective in reducing microbe generated VOCs in AHU SPECIFICATIONS Model See Table 1 Electrical ...

Page 2: ...shows a crossed out wheelie bin as required by law regarding the Waste of Electrical and Electronic Equipment WEEE disposal This indicates your responsibility to contribute in saving the environment by proper disposal of this Waste i e do not dispose of this product with your other wastes To know the right disposal mechanism please check the applicable law Table 1 HUVF Series Models Fig 1 Dual lam...

Page 3: ... are cooling coils or other surfaces that require ultraviolet treatment When used in an AHU the installation shall be done between the pre filters and cooling coil in such a way that the lamps are facing towards the cooling coil Fig 3 HUVF positioning inside AHU Fig 4 Array detail view Constructing the Array Multiple systems can be nut and bolted to each other either side by side or on top of othe...

Page 4: ...equipment INSTALLATION When Installing This Product 1 The UV system is designed only for use inside Air Handling Units AHU and Air ducts The units must not be used in any other location or manner The manufacturer will not be responsible for the perfor mance of the system or any hazard to health by its use in an unintended manner 2 The UV system must be installed inside the AHU or air duct An inter...

Page 5: ...ates an earth connection for functional purposes only Power Connections 1 Decide which end of the installed array is most acces sible for wiring 2 Cut off the plastic connector for each row of air cleaners on the end selected 3 Install a extension box to the end of each row of air cleaners 4 Connect power and ground leads to each row of air cleaners 5 Install cover on each box 6 Install box and co...

Page 6: ...idal effectiveness The visible blue light will continue to illuminate but does not have any germicidal effectiveness Bulbs must be replaced on schedule for the system to function properly IMPORTANT Use only Honeywell replacement lamps Use of replacement lamps from other manufacturers voids the warranty See Table 2 for replacement lamp part numbers For replacing the lamp s on the HUVF series first ...

Page 7: ...human being and hence the system must have interlock with the access door so that when the access door is opened the system power supply will cut All the systems installed inside the AHU will be powered up by the single power cable Please disconnect the power supply before servicing the unit Check the input power cable looping using continuity tester and confirm that all the looping wires show con...

Page 8: ... District Centre Jasola NEW DELHI 110025 India 1 800 103 4761 Honeywell Building Technologies Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 0 7031 637 01 Fax 49 0 7031 637 740 buildings honeywell com customer honeywell com U S Registered Trademark 2020 Honeywell International Inc 31 00455 01 M S 11 20 Printed in United States ...

Reviews: