background image

HUVF SERIES DUCT MOUNTED UV SYSTEM

5

31-00455—01

Connect the Lamps

WARNING

Breakable Glass Hazard.
Can cause personal injury.

Be careful when inserting bulb(s) into lamp base. 
Wear protective gloves when handling the bulb(s).

MERCURY NOTICE

This device contains mercury in the sealed 
ultraviolet bulb(s). Do not place your used bulb(s) in 
the trash. Dispose of properly.

Make sure that the UV lamp is connected properly to the 
4-pin holder and is fixed in the clamps provided on the 
reflector as shown in Fig. 7 below

Fig. 7. Bulb connection.

WIRING

WARNING

Main power supply must be secured with 
interlock on the AHU door.

The electrical supply circuit connected to this UV 
appliance must be routed through an electrical 
interlock switch placed on the HVAC system duct 
access panels and doors to prevent accidental UV 
exposure when servicing the air ducts or 
equipment. Interlock shall break all supply 
conductors.

• Power supply wiring system shall provide a 

disconnect switch for all poles.

• Assure all wiring complies with local codes and 

ordinances.

• Wire the UV system directly to the correct voltage 

and frequency electrical source. See Fig. 8.

• Install extension box, with cover, for all external 

plugs and wiring connections.

• This appliance incorporates an earth connection 

for functional purposes only.

Power Connections

1.

Decide which end of the installed array is most acces-
sible for wiring.

2.

Cut off the plastic connector for each row of air 
cleaners on the end selected.

3.

Install a extension box to the end of each row of air 
cleaners.

4.

Connect power and ground leads to each row of air 
cleaners.

5.

Install cover on each box.

6.

Install box and cover over power connector on oppo-
site end of each row.

Fig. 8. Power connection to HUVF.

OPERATION AND 
MAINTENANCE

NOTICE:

• Service of the product to be done by authorized 

representative only 

• Operated and serviced by qualified personnel
• No interlocks under any circumstance are defeated
• All safety measures recommended are followed as 

prescribed 

• Provided all control measures are implemented at the 

user site for safety as per the Risk analysis document.

• Any internal part of the assembly shall not be removed 

for independent use for other applications.

During normal operation make sure that the electrical 
supply circuit connected to this UV appliance must be 
routed through an electrical interlock switch placed on the 
HVAC system duct access panels and doors to prevent 
accidental UV exposure when servicing the air ducts or 
equipment” or equivalent. “Interlock shall break all supply 
conductors.

1

2

3

Power Input

Adjacent System

F

M

M

M = Male Connector

F = Female Connector

 

Adjacent 
System

HUVF58C1000 / HUVF58C2000

HUVF58S1000 / HUVF58S2000

Summary of Contents for HUVF Series

Page 1: ... AHU near Cooling coil Plug and Play design enables ease of installation Effective on all types of pathogens HUVF58C2000 HUVF58S2000 2 Lamps 23W max each HUVF58C1000 HUVF58S1000 1 Lamp 23W max Effective in IAQ improvement Effective deactivation of viruses and bacteria killing with 254 nm wavelength UVC Effective in reducing microbe generated VOCs in AHU SPECIFICATIONS Model See Table 1 Electrical ...

Page 2: ...shows a crossed out wheelie bin as required by law regarding the Waste of Electrical and Electronic Equipment WEEE disposal This indicates your responsibility to contribute in saving the environment by proper disposal of this Waste i e do not dispose of this product with your other wastes To know the right disposal mechanism please check the applicable law Table 1 HUVF Series Models Fig 1 Dual lam...

Page 3: ... are cooling coils or other surfaces that require ultraviolet treatment When used in an AHU the installation shall be done between the pre filters and cooling coil in such a way that the lamps are facing towards the cooling coil Fig 3 HUVF positioning inside AHU Fig 4 Array detail view Constructing the Array Multiple systems can be nut and bolted to each other either side by side or on top of othe...

Page 4: ...equipment INSTALLATION When Installing This Product 1 The UV system is designed only for use inside Air Handling Units AHU and Air ducts The units must not be used in any other location or manner The manufacturer will not be responsible for the perfor mance of the system or any hazard to health by its use in an unintended manner 2 The UV system must be installed inside the AHU or air duct An inter...

Page 5: ...ates an earth connection for functional purposes only Power Connections 1 Decide which end of the installed array is most acces sible for wiring 2 Cut off the plastic connector for each row of air cleaners on the end selected 3 Install a extension box to the end of each row of air cleaners 4 Connect power and ground leads to each row of air cleaners 5 Install cover on each box 6 Install box and co...

Page 6: ...idal effectiveness The visible blue light will continue to illuminate but does not have any germicidal effectiveness Bulbs must be replaced on schedule for the system to function properly IMPORTANT Use only Honeywell replacement lamps Use of replacement lamps from other manufacturers voids the warranty See Table 2 for replacement lamp part numbers For replacing the lamp s on the HUVF series first ...

Page 7: ...human being and hence the system must have interlock with the access door so that when the access door is opened the system power supply will cut All the systems installed inside the AHU will be powered up by the single power cable Please disconnect the power supply before servicing the unit Check the input power cable looping using continuity tester and confirm that all the looping wires show con...

Page 8: ... District Centre Jasola NEW DELHI 110025 India 1 800 103 4761 Honeywell Building Technologies Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 0 7031 637 01 Fax 49 0 7031 637 740 buildings honeywell com customer honeywell com U S Registered Trademark 2020 Honeywell International Inc 31 00455 01 M S 11 20 Printed in United States ...

Reviews: