background image

HUVF SERIES DUCT MOUNTED UV SYSTEM

3

31-00455—01

PLANNING THE 
INSTALLATION

NOTICE:

• Read the maintenance instructions before opening the 

appliance.

• Appliances that are obviously damaged must not be 

operated.

• UV-C BARRIERS bearing the ULTRAVIOLET RADIATION 

hazard symbol should not be removed.

• Do not operate UV-C LAMPS outside of the appliance.

Choosing a Mounting Position

CAUTION

Equipment Damage Hazard.

Ultraviolet light can cause color shift or surface 
degradation and sometimes structural degradation 
of non-metallic components. Select mounting 
location that prevents exposure to plastic flexible 
duct components, polyurethane foam insulation 
material, rubber hoses, wire insulation, etc. If 
mounting options are limited, items above should 
be protected with ultraviolet resistant material such 
as aluminum foil, aluminum duct tape, or metallic 
shields or the equivalent.

The HUVF Series is used in forced air heating, cooling, or 
ventilating systems. The system is mounted in the air 
handling unit (AHU) or ductwork where there are cooling 
coils or other surfaces that require ultraviolet treatment. 
When used in an AHU, the installation shall be done 
between the pre-filters and cooling coil in such a way that 
the lamps are facing towards the cooling coil. 

Fig. 3. HUVF positioning inside AHU.

Fig. 4. Array detail view.

Constructing the Array

Multiple systems can be nut and bolted to each other, 
either side by side or on top of other, to fill the cross section 
of the ductwork or air-handling unit where the UV system is 
being installed. If each system is individually supported by 
the array support structure it is not necessary to connect 
the systems to each other. The system can be connected to 
each other as shown in the diagram below. Two or more 
systems can be connected side by side, and when required 
multiple rows can be placed on top of each other. 

The male and female connectors are used for powering the 
systems. A common 230 Vac single phase power source 
shall be used for powering the array. The power shall not be 
turned 'ON' until all the mechanical fitment is finished, 
refer to WIRING section at the end of installation for mains 
power connection.

AIR OUT

Detail Arrangement

AIR IN

HUVF Series

Blower

Cooling Coil

Pre Filter/F58 Series EAC

Summary of Contents for HUVF Series

Page 1: ... AHU near Cooling coil Plug and Play design enables ease of installation Effective on all types of pathogens HUVF58C2000 HUVF58S2000 2 Lamps 23W max each HUVF58C1000 HUVF58S1000 1 Lamp 23W max Effective in IAQ improvement Effective deactivation of viruses and bacteria killing with 254 nm wavelength UVC Effective in reducing microbe generated VOCs in AHU SPECIFICATIONS Model See Table 1 Electrical ...

Page 2: ...shows a crossed out wheelie bin as required by law regarding the Waste of Electrical and Electronic Equipment WEEE disposal This indicates your responsibility to contribute in saving the environment by proper disposal of this Waste i e do not dispose of this product with your other wastes To know the right disposal mechanism please check the applicable law Table 1 HUVF Series Models Fig 1 Dual lam...

Page 3: ... are cooling coils or other surfaces that require ultraviolet treatment When used in an AHU the installation shall be done between the pre filters and cooling coil in such a way that the lamps are facing towards the cooling coil Fig 3 HUVF positioning inside AHU Fig 4 Array detail view Constructing the Array Multiple systems can be nut and bolted to each other either side by side or on top of othe...

Page 4: ...equipment INSTALLATION When Installing This Product 1 The UV system is designed only for use inside Air Handling Units AHU and Air ducts The units must not be used in any other location or manner The manufacturer will not be responsible for the perfor mance of the system or any hazard to health by its use in an unintended manner 2 The UV system must be installed inside the AHU or air duct An inter...

Page 5: ...ates an earth connection for functional purposes only Power Connections 1 Decide which end of the installed array is most acces sible for wiring 2 Cut off the plastic connector for each row of air cleaners on the end selected 3 Install a extension box to the end of each row of air cleaners 4 Connect power and ground leads to each row of air cleaners 5 Install cover on each box 6 Install box and co...

Page 6: ...idal effectiveness The visible blue light will continue to illuminate but does not have any germicidal effectiveness Bulbs must be replaced on schedule for the system to function properly IMPORTANT Use only Honeywell replacement lamps Use of replacement lamps from other manufacturers voids the warranty See Table 2 for replacement lamp part numbers For replacing the lamp s on the HUVF series first ...

Page 7: ...human being and hence the system must have interlock with the access door so that when the access door is opened the system power supply will cut All the systems installed inside the AHU will be powered up by the single power cable Please disconnect the power supply before servicing the unit Check the input power cable looping using continuity tester and confirm that all the looping wires show con...

Page 8: ... District Centre Jasola NEW DELHI 110025 India 1 800 103 4761 Honeywell Building Technologies Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 0 7031 637 01 Fax 49 0 7031 637 740 buildings honeywell com customer honeywell com U S Registered Trademark 2020 Honeywell International Inc 31 00455 01 M S 11 20 Printed in United States ...

Reviews: