HUVF SERIES DUCT MOUNTED UV SYSTEM

31-00455—01

4

Fig. 5. Array interconnections.

Constructing Array Support 
Structure

WARNING

Construction Collapse Hazard.

Can cause personal injury or equipment damage. 
Provide adequate structural support to prevent 
array collapse. Support each unit with external 
structural elements across both top and bottom and 
add cross supports, as needed. 

Provide adequate array support to prevent collapse:
• Provide minimum of external structural support 

across the top and bottom of each unit.

• Provide cross supports, as needed.

Fig. 6. Array support structure.

WARNING

UV Light Hazard.
Harmful to bare skin and eyes.
Can cause temporary or permanent loss of vision.

Do not look at the UV lamp when lighting is on. Use 
indicator light on the ballast to check status. In 
order to prevent exposure to UV light, before repair 
of any parts of HVAC system, shut off power supply 
to UV system. Do not install in a position where UV 
lamp is visible during normal operation of HVAC 
equipment.

INSTALLATION

When Installing This Product… 

1.

The UV system is designed only for use inside Air 
Handling Units (AHU) and Air ducts. The units must 
not be used in any other location or manner. The 
manufacturer will not be responsible for the perfor-
mance of the system or any hazard to health by its 
use in an unintended manner.

2.

The UV system must be installed inside the AHU or air 
duct. An interlock switch to turn off the UV system 
should be provided during installation that turned off 
the UV system in the event the AHU is opened or 
accessed to prevent exposure to humans.

3.

Proper PPE and UV eye protection to be used during 
installation of the system, UV rays are harmful to the 
human skin and eyes, care must be taken to ensure 
no direct exposure.

4.

Testing of lamps other than once installed inside an 
AHU fitted with an interlock switch should only be 
done inside custom built fully enclosed test equip-
ment.

5.

The installation, service and maintenance of the sys-
tem must be carried out by the qualified personnel of 
authorized representative.

F

M

F

M

F

M

F

M

M

M

M

M

Power Connection

To adjacent unit

CROSS SUPPORTS

 ATTACHED TO DUCT FLANGE

AIR HANDLER 

DUCT FLANGE

M13457

Summary of Contents for HUVF Series

Page 1: ... AHU near Cooling coil Plug and Play design enables ease of installation Effective on all types of pathogens HUVF58C2000 HUVF58S2000 2 Lamps 23W max each HUVF58C1000 HUVF58S1000 1 Lamp 23W max Effective in IAQ improvement Effective deactivation of viruses and bacteria killing with 254 nm wavelength UVC Effective in reducing microbe generated VOCs in AHU SPECIFICATIONS Model See Table 1 Electrical ...

Page 2: ...shows a crossed out wheelie bin as required by law regarding the Waste of Electrical and Electronic Equipment WEEE disposal This indicates your responsibility to contribute in saving the environment by proper disposal of this Waste i e do not dispose of this product with your other wastes To know the right disposal mechanism please check the applicable law Table 1 HUVF Series Models Fig 1 Dual lam...

Page 3: ... are cooling coils or other surfaces that require ultraviolet treatment When used in an AHU the installation shall be done between the pre filters and cooling coil in such a way that the lamps are facing towards the cooling coil Fig 3 HUVF positioning inside AHU Fig 4 Array detail view Constructing the Array Multiple systems can be nut and bolted to each other either side by side or on top of othe...

Page 4: ...equipment INSTALLATION When Installing This Product 1 The UV system is designed only for use inside Air Handling Units AHU and Air ducts The units must not be used in any other location or manner The manufacturer will not be responsible for the perfor mance of the system or any hazard to health by its use in an unintended manner 2 The UV system must be installed inside the AHU or air duct An inter...

Page 5: ...ates an earth connection for functional purposes only Power Connections 1 Decide which end of the installed array is most acces sible for wiring 2 Cut off the plastic connector for each row of air cleaners on the end selected 3 Install a extension box to the end of each row of air cleaners 4 Connect power and ground leads to each row of air cleaners 5 Install cover on each box 6 Install box and co...

Page 6: ...idal effectiveness The visible blue light will continue to illuminate but does not have any germicidal effectiveness Bulbs must be replaced on schedule for the system to function properly IMPORTANT Use only Honeywell replacement lamps Use of replacement lamps from other manufacturers voids the warranty See Table 2 for replacement lamp part numbers For replacing the lamp s on the HUVF series first ...

Page 7: ...human being and hence the system must have interlock with the access door so that when the access door is opened the system power supply will cut All the systems installed inside the AHU will be powered up by the single power cable Please disconnect the power supply before servicing the unit Check the input power cable looping using continuity tester and confirm that all the looping wires show con...

Page 8: ... District Centre Jasola NEW DELHI 110025 India 1 800 103 4761 Honeywell Building Technologies Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 0 7031 637 01 Fax 49 0 7031 637 740 buildings honeywell com customer honeywell com U S Registered Trademark 2020 Honeywell International Inc 31 00455 01 M S 11 20 Printed in United States ...