background image

HUVF SERIES DUCT MOUNTED UV SYSTEM

31-00455—01

6

During normal operation the lamps need to be cleaned 
once or twice in a month to make sure that there is no dust 
accumulation on the lamp surface. This cleaning can be 
done by normal wiping cloth or tissue paper. Make sure 
that the lamp mounted on the reflector clips is tight 
enough so that it remains in the same position before and 
after cleaning.

Do not pour / splash / spill water on the system and lamps 
during the coil cleaning. In case of accidental spillage of 
water on the system make sure that the system is wiped 
with a dry cloth to remove the water droplets. Do not switch 
ON the UV system immediately, instead run the blower and 
the HVAC system for some time (15-20 minutes) and then 
switch ON the UV system.

Replace as per lamp life issued in the documentation.

SERVICE

Lamp Replacement

WARNING

Breakable Glass Hazard.
Can cause personal injury.

Be careful when inserting bulb(s) into lamp base. 
Wear protective gloves when handling the bulb(s). 

MERCURY NOTICE

This device contains mercury in the sealed 
ultraviolet bulb(s). Do not place your used bulb(s) in 
the trash. Dispose of properly.

The UV lamps are rated for 12,000 hours of germicidal 
effectiveness. The visible blue light will continue to 
illuminate but does not have any germicidal effectiveness. 
Bulbs must be replaced on schedule for the system to 
function properly. 

IMPORTANT

Use only Honeywell replacement lamps. Use of 
replacement lamps from other manufacturers 
voids the warranty. See Table 2 for repl
acement 
lamp part numbers.

For replacing the lamp(s) on the HUVF series first 
disconnect the power of the system. Remove the 4-pin 
holder on top of the lamp by pulling the lamp out of the 

fixture clamps. Connect the new lamp in the 4-pin holder 
and fix the lamp in the SS clamps. Refer to Fig. 3 in the 
INSTALLATION section. 

Ballast Replacement

Refer to internal wiring diagrams.

Fig. 9. Wiring diagram for HUVF58C1000 and 

HUVF58S1000.

Fig. 10. Wiring diagram for HUVF58C2000 and 

HUVF58S2000.

Disconnect the line, neutral, earthing wire and lamp wires 
from the ballast making note of the color code and position 
of each wire. Back out the screws and remove the old 
ballast from the L plate.

After removing the old ballast place new ballast on the L 
plate and replace the mounting screws. Reconnect the 
power and lamp cable wires as per color coding. Ballast 
replacement is complete.

Fig. 11. Ballast Wiring.

Connectwell Connector

F

M

VEGO Connector

M

BALLAST

4

Pin

Holder

Connectwell Connector

F

M

VEGO Connector

M

BALLAST

4

Pin

Holder

4

Pin

Holder

ELECTRONIC BALLAST FOR UV LAMPS

Summary of Contents for HUVF Series

Page 1: ... AHU near Cooling coil Plug and Play design enables ease of installation Effective on all types of pathogens HUVF58C2000 HUVF58S2000 2 Lamps 23W max each HUVF58C1000 HUVF58S1000 1 Lamp 23W max Effective in IAQ improvement Effective deactivation of viruses and bacteria killing with 254 nm wavelength UVC Effective in reducing microbe generated VOCs in AHU SPECIFICATIONS Model See Table 1 Electrical ...

Page 2: ...shows a crossed out wheelie bin as required by law regarding the Waste of Electrical and Electronic Equipment WEEE disposal This indicates your responsibility to contribute in saving the environment by proper disposal of this Waste i e do not dispose of this product with your other wastes To know the right disposal mechanism please check the applicable law Table 1 HUVF Series Models Fig 1 Dual lam...

Page 3: ... are cooling coils or other surfaces that require ultraviolet treatment When used in an AHU the installation shall be done between the pre filters and cooling coil in such a way that the lamps are facing towards the cooling coil Fig 3 HUVF positioning inside AHU Fig 4 Array detail view Constructing the Array Multiple systems can be nut and bolted to each other either side by side or on top of othe...

Page 4: ...equipment INSTALLATION When Installing This Product 1 The UV system is designed only for use inside Air Handling Units AHU and Air ducts The units must not be used in any other location or manner The manufacturer will not be responsible for the perfor mance of the system or any hazard to health by its use in an unintended manner 2 The UV system must be installed inside the AHU or air duct An inter...

Page 5: ...ates an earth connection for functional purposes only Power Connections 1 Decide which end of the installed array is most acces sible for wiring 2 Cut off the plastic connector for each row of air cleaners on the end selected 3 Install a extension box to the end of each row of air cleaners 4 Connect power and ground leads to each row of air cleaners 5 Install cover on each box 6 Install box and co...

Page 6: ...idal effectiveness The visible blue light will continue to illuminate but does not have any germicidal effectiveness Bulbs must be replaced on schedule for the system to function properly IMPORTANT Use only Honeywell replacement lamps Use of replacement lamps from other manufacturers voids the warranty See Table 2 for replacement lamp part numbers For replacing the lamp s on the HUVF series first ...

Page 7: ...human being and hence the system must have interlock with the access door so that when the access door is opened the system power supply will cut All the systems installed inside the AHU will be powered up by the single power cable Please disconnect the power supply before servicing the unit Check the input power cable looping using continuity tester and confirm that all the looping wires show con...

Page 8: ... District Centre Jasola NEW DELHI 110025 India 1 800 103 4761 Honeywell Building Technologies Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 0 7031 637 01 Fax 49 0 7031 637 740 buildings honeywell com customer honeywell com U S Registered Trademark 2020 Honeywell International Inc 31 00455 01 M S 11 20 Printed in United States ...

Reviews: