HUVF SERIES DUCT MOUNTED UV SYSTEM

7

31-00455—01

ELECTRICAL 
TROUBLESHOOTING

WARNING

Electric Shock Hazard.

Can cause personal injury or equipment damage. 
The following procedures expose hazardous live 
parts and are for use only by qualified personnel. 
Disconnect power between checks and proceed 
carefully.

Tools and Equipment

Tools to be used for electrical troubleshooting:
• Continuity tester.
• PPE  Kit

Troubleshooting Procedure

The power supply to the system is connected using plug 
and play connector arrangement. Make sure that proper 
PPE are used before start of any testing. Please note that 
UV is harmful to human being and hence the system must 
have interlock with the access door, so that when the 
access door is opened the system power supply will cut. All 
the systems installed inside the AHU will be powered up by 
the single power cable. Please disconnect the power supply 
before servicing the unit. 

Check the input power cable looping using continuity 
tester and confirm that all the looping wires show 
continuity during power off condition. Make sure that 
interlock is in place once the servicing is completed. Once 
the access door is closed, switch ON the power supply so 
that system starts working again.    

PARTS LIST

Table 2. HUVF Parts List.

Model

Lamp

Lamp Qty.

Ballast

Holder

HUVF58C1000

HUVL58C0000

1

HUVB5801000

HUVB58K1000

HUVF58C2000

2

HUVB5802000

HUVF58S1000

HUVL58S0000

1

HUVB5801000

HUVF58S2000

2

HUVB5802000

Summary of Contents for HUVF Series

Page 1: ... AHU near Cooling coil Plug and Play design enables ease of installation Effective on all types of pathogens HUVF58C2000 HUVF58S2000 2 Lamps 23W max each HUVF58C1000 HUVF58S1000 1 Lamp 23W max Effective in IAQ improvement Effective deactivation of viruses and bacteria killing with 254 nm wavelength UVC Effective in reducing microbe generated VOCs in AHU SPECIFICATIONS Model See Table 1 Electrical ...

Page 2: ...shows a crossed out wheelie bin as required by law regarding the Waste of Electrical and Electronic Equipment WEEE disposal This indicates your responsibility to contribute in saving the environment by proper disposal of this Waste i e do not dispose of this product with your other wastes To know the right disposal mechanism please check the applicable law Table 1 HUVF Series Models Fig 1 Dual lam...

Page 3: ... are cooling coils or other surfaces that require ultraviolet treatment When used in an AHU the installation shall be done between the pre filters and cooling coil in such a way that the lamps are facing towards the cooling coil Fig 3 HUVF positioning inside AHU Fig 4 Array detail view Constructing the Array Multiple systems can be nut and bolted to each other either side by side or on top of othe...

Page 4: ...equipment INSTALLATION When Installing This Product 1 The UV system is designed only for use inside Air Handling Units AHU and Air ducts The units must not be used in any other location or manner The manufacturer will not be responsible for the perfor mance of the system or any hazard to health by its use in an unintended manner 2 The UV system must be installed inside the AHU or air duct An inter...

Page 5: ...ates an earth connection for functional purposes only Power Connections 1 Decide which end of the installed array is most acces sible for wiring 2 Cut off the plastic connector for each row of air cleaners on the end selected 3 Install a extension box to the end of each row of air cleaners 4 Connect power and ground leads to each row of air cleaners 5 Install cover on each box 6 Install box and co...

Page 6: ...idal effectiveness The visible blue light will continue to illuminate but does not have any germicidal effectiveness Bulbs must be replaced on schedule for the system to function properly IMPORTANT Use only Honeywell replacement lamps Use of replacement lamps from other manufacturers voids the warranty See Table 2 for replacement lamp part numbers For replacing the lamp s on the HUVF series first ...

Page 7: ...human being and hence the system must have interlock with the access door so that when the access door is opened the system power supply will cut All the systems installed inside the AHU will be powered up by the single power cable Please disconnect the power supply before servicing the unit Check the input power cable looping using continuity tester and confirm that all the looping wires show con...

Page 8: ... District Centre Jasola NEW DELHI 110025 India 1 800 103 4761 Honeywell Building Technologies Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 0 7031 637 01 Fax 49 0 7031 637 740 buildings honeywell com customer honeywell com U S Registered Trademark 2020 Honeywell International Inc 31 00455 01 M S 11 20 Printed in United States ...

Reviews: