HVAC400X – APPLICATION MANUAL
17
EN2B-0417GE51 R0719
2.4
Resonance Sweep Wizard
Use these instructions to start the resonance sweep function.
STARTING THE RESONANCE SWEEP FUNCTION
1.
Find parameter P3.7.9 and press the OK button. Para-
meter 3.7.9 is not visible in the software – as you would
normally expect – but rather only in the display.
2.
Use the UP and DOWN arrow buttons to select value 1
"Activate" and press the OK button.
3.
When the text "Start sweep" appears, press the Start
button. The sweeping starts.
4.
Press the OK button each time the resonance stops to
mark where the range starts and ends.
STOP
READY
I/O
Resonance Sweep
P 3.7.9
ID: 1811
Inactive
Activate
STOP
READY
I/O
Resonance Sweep
P 3.7.9
ID: 1811
Inactive
Activate
STOP
READY
Keypad
ID:
Start Sweep!
RUN
READY
Keypad
ID: 1
28.09 Hz
Output Frequency