HVAC400X – APPLICATION MANUAL
55
EN2B-0417GE51 R0719
5.8
Group 3.8: Limit Supervisions
Table 25. Limits supervision settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.8.1
Supervision #1 Item
Selection
0
7
0
1431
0 = Output frequency.
1 = Frequency reference.
2 = Motor current.
3 = Motor torque.
4 = Motor power.
5 = DC-link voltage.
6 = Analog input 1.
7 = Analog input 2.
P3.8.2
Supervision #1 Mode
0
2
0
1432
0 = Not used.
1 = Low limit supervision (output active
under limit).
2 = High limit supervision (output
active over limit).
P3.8.3
Supervision #1 Limit
Varies
Varies
Varies
25.00
1433
P3.8.4
Supervision #1 Limit
Hysteresis
Varies
Varies
Varies
5.00
1434
P3.8.5
Supervision #2 Item
Selection
0
7
1
1435
See P3.8.1.
P3.8.6
Supervision #2 Mode
0
2
0
1436
See P3.8.2.
P3.8.7
Supervision #2 Limit
Varies
Varies
Varies
40.00
1437
See P3.8.3.
P3.8.8
Supervision #2 Limit
Hysteresis
Varies
Varies
Varies
5.00
1438
See P3.8.4.