5
STEP 3 – Program the Communicator
The HWF2-COM requires an AlarmNet account. For new installations, please obtain the account information from the
central station prior to programming.
You can program the communicator by one of the following methods:
•
Using the AlarmNet 360 website.
•
Using the 7720P Programming Tool.
•
Using the control panel's programming mode (for panels that support this option) to access the communicator's pro-
gramming.
NOTE:
The prompts in this document reflect use of the 7720P Programming Tool.
Using the AlarmNet 360 Website
To program the communicator via the website (if you are already signed up for this service), go to:
www.alamnet360.com
Please have the following information available when programming the communicator:
•
Primary City ID (two-digit number), obtained from your monitoring station.
•
Primary Central Station ID (two-digit number), obtained from your monitoring station.
•
Primary Subscriber ID (four-digit number), obtained from your monitoring station.
•
Communicator’s MAC ID and MAC CRC number (located on the box and inside the communicator).
After programming is complete, the communicator must be registered. Refer to the
Register the Module
topic.
When using the 7720P Programming tool, the values given below are for most installations. Press the
[#]
key to accept the
displayed default value (xxx) or enter the new value and press the [#] key for the next prompt. Use the [Space] key to scroll
through a list of options.
1.
Connect the 7720P. (You can use the [Shift + A] key to check the software revision.)
2.
7720P PROGRAMMER
Press [#].
3.
Start Prog Mode? Y/N
Press [Shift] then [Y], then [#].
4.
Program Device? Y/N
Press [Shift] then [Y], then [#].
5.
Com Path Choice (IP & Cell)
Press [Space] to scroll choices; IP&Cell, IP, or Cell. Press [#] to select.
The IP Fault Time, and the Cell Fault Time that correspond to the choices are:
Choice
Supervision Interval
IP Fault Time
Cell Fault Time
2010 IP & Cell
24 hours
1 hour
1 hour
2013 IP
1 hour
1 hour
- - -
2013 Cell
1 hour
- - -
1 hour
2013 IP & Cell
6 hours
1 hour
1 hour
2010 IP
5 minutes
5 minutes
- - -
2010 Cell
5 minutes
- - -
5 minutes
6.
Primary City ID (??)
Enter number 01-99, then press [#].
7.
Primary CS ID (??)
Enter number 01-FE, then press [#].
8.
Primary Sub ID (????)
Enter number 0001-9999, then press [#].
9.
Cell Flt Time
(60 mins)
NOTE:
Refer to table above
for correct default values.
This prompt appears only if comm. path includes IP&Cell or Cell.
Enter the time delay (1 – 60) in minutes before the communicator notifies the con-
trol there is a communication path failure to AlarmNet over cell. If the panel has an
alternate communication path, a secondary path loss message is sent to the cen-
tral station.
NOTE:
The 2013 choices
have been evaluated to
meet NFPA 2013 super-
vision requirements and
are subject to approval by
the local authority having
jurisdiction.
Summary of Contents for HWF2A-COM
Page 21: ...19 Communicator Information ...
Page 24: ...22 NOTES ...
Page 25: ...23 NOTES ...
Page 26: ...24 NOTES ...