Figure 3-1 General Layout
Remember, the approximate line of sight range between a Transmitter and Base Radio is
determined by the Baud Rate as listed below:
76.8K -76.8 Kbaud, Range of 500 to 750 ft
•
•
•
19.2K - 19.2 Kbaud, Range of 2,000 to 2,500 ft
4.8K - 4.8 Kbaud, Range of 3,000 ft
Note
This range is reduced by the amount of RF Noise present, obstructions, and the
material properties of those obstructions.
Only place the Base Radio in ambient operating temperatures of -40°F to 185°F (-40°C to
85°C).
Make sure you have power and communication to the Base Radio available (see 3.2
Electrical Installation).
Because there are so many setup possibilities we cannot cover them all. A correct setup
would make sure that the above warnings are heeded and that the Transmitter and Base
Radio are capable of communication. The RF Placement Procedure section of the
Transmitter Guide will help you to determine if you have a selected the correct installation
points and orientations for your application.