background image

L7124U UNIVERSAL OIL ELECTRONIC AQUASTAT® CONTROLLER

5

69-1232—2

OPERATION

High Limit Controller

The high limit opens and turns off the burner when the 
water temperature reaches the setpoint. The high limit 
automatically resets after the water temperature drops 
past the setpoint and through the 15°F (8°C) differential.

Low Limit and Circulator Controller

On a temperature rise, with the adjustable differential at 
the minimum setting of 10°F (6°C), the burner circuit 
breaks and the circulator circuit makes at the low limit 
setpoint. On a temperature drop of 10°F (6°C) below the 
low limit setpoint, the burner circuit makes and the 
circulator circuit breaks. See Fig. 5.

CAUTION

Equipment Damage Hazard.
Can cause improper operation 

1. Setting the Low Limit above the High Limit 

disables the device.

2. Setting the Low Limit less than 15°F (8°C) 

below the High Limit results in improper 
circulator function.

Fig. 5. Setpoints and differentials.

The L7124U can be in any of four operational states: 
Normal, High-Limit, Low-Limit and Error. The controller 
moves back and forth from High-Limit to Normal to 
Low-Limit state as part of normal operation. However, the 
controller enters only  the Error state when there is an 
abnormal condition such as an internal error or a bad 
sensor. The operating states are:

1.

Normal: Boiler temperature has gone below the 
high limit setting (minus the fixed differential) and 
has not exceeded the high limit setting; or, the 
boiler temperature has gone above the low limit 
setting and has not gone below the low limit setting 
(minus the fixed differential).

2.

High-Limit: Boiler temperature has gone above the 
high limit setting and has not dropped below the 
high limit setting (minus the fixed differential).

3.

Low-Limit: Boiler temperature has gone below the 
low limit setting (minus the low limit differential) and 
has not gone above the low limit setting.

4.

Error: The controller has detected an error 
condition (e.g., open sensor) and has shut down 
the burner output. The circulator and ZC output are 
energized. The controller  continues to function 
and automatically restarts if the error condition 
clears.

The operating sequence for the L7124U is shown in
Table 2.

CHECKOUT

Put the system into operation and observe operation 
through at least one complete cycle to make sure that the 
controller operates properly.

Table 2. L7124U Controller Operating Sequence.

LOW LIMIT 
SETTING

HIGH LIMIT
SETTING

SWITCH BREAKS ON 
TEMPERATURE RISE. 
BURNER TURNS OFF. 
CIRCULATOR OPERATES 
ON A CALL FOR HEAT.

SWITCH MAKES ON 
TEMPERATURE FALL.
BURNER OPERATES ON A 
CALL FOR HEAT.

WITH NO HEATING 
DEMAND, SWITCH  BREAKS 
ON TEMPERATURE RISE.

SWITCH MAKES ON 
TEMPERATURE FALL, 
BURNER IS ON TO 
MAINTAIN MINIMUM 
WATER TEMPERATURE. 
CIRCULATOR IS OFF.

M21059

WHEN WATER REACHES LOW LIMIT SETTING, THE BURNER SHUTS 
OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING FOR HEAT).

1

1

Action

System Response

Thermostat 
calls for 
heat.

Circulator starts when water temperature is 
above low limit setting (if applicable).
Boiler temperature is checked.
Burner starts when  water temperature is 
below high limit setting and above low limit 
setting.

Boiler 
exceeds the 
high limit.

Burner is turned off. Burner restarts when 
the water temperature drops below  the 
high limit setting minus the differential.

Thermostat 
is satisfied.

Circulator and burner turn off.

Error 
condition.

When an error  condition is detected, all 
outputs except C and ZC are shut down. 
Burner is off. Control continues to function 
and restarts when error is corrected. 
During the error check sequence, the 
system checks for drift in the sensor and 
corrosion in the connections.

Summary of Contents for L7124U

Page 1: ... mechanical distance Some models also have a Low Limit and Low Limit Differential adjustment The range of the Low Limit dial is from 110 F to 220 F 43 C to 104 C Rotating the Low Limit potentiometer fully counterclockwise disables the low limit function and turns on the Low Limit Disabled LED The L7124U is designed for use with 24 Vac electronic and electromechanical thermostats and has screw type...

Page 2: ...e flange on the well 9 Securely tighten the clamp screw IMPORTANT Best thermal response is obtained with a well that snugly fits the sensor Insert the sensor until it rests against the bottom of the well use a well of correct length and bend the wiring if necessary to hold the bulb against the bottom of the well If the well is not a snug fit on the sensor use the heat conductive compound furnished...

Page 3: ...proved for use with copper wire only Follow the appropriate wiring diagrams shown on the inside of the front cover of the L7124U or in Fig 3 and 4 Fig 3 L7124U single zone connections SENSOR WIRES IMMERSION WELL CLAMP SCREW IMMERSION WELL CLAMP M16120 HEAT CONDUCTIVE COMPOUND OPTIONAL CONTROLLER CASE BOILER IMMERSION WELL SENSOR LOW LIMIT HIGH LIMIT DIFF SENSOR PWR T L2 T TSTAT DSBL LL B B2 B1 C2 ...

Page 4: ...CULATOR TO ADDITIONAL R845A RELAYS FOR OTHER ZONES LOW LIMIT HIGH LIMIT DIFF SENSOR PWR T L2 T TSTAT DSBL LL B B2 B1 C2 ZR ZC C1 C ZC 1 2 M17777 1 1 2 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONTROL CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED LINE VOLTAGE OIL BURNER RELAY LINE VOLTAGE CIRCULATOR LOW VOLTAGE THERMOSTAT T1 LEGEND LED SENSOR...

Page 5: ...he fixed differential 3 Low Limit Boiler temperature has gone below the low limit setting minus the low limit differential and has not gone above the low limit setting 4 Error The controller has detected an error condition e g open sensor and has shut down the burner output The circulator and ZC output are energized The controller continues to function and automatically restarts if the error condi...

Page 6: ...System Condition Check Corrective Action Boiler is cold house is cold PWR LED Off Check 120 Vac system power 1A fuse on L7124U PWR LED On TSTAT LED Off Check Thermostat Thermostat wiring PWR LED On TSTAT LED On B burner LED On Check 120 Vac B1 B2 If no replace burner relay If yes check burner and wiring PWR LED On TSTAT LED On LL DSBL LED Flashing Refer to LED diagnostics Table 3 Boiler is hot hou...

Page 7: ...7 69 1232 2 ...

Page 8: ... on recycled paper containing at least 10 post consumer paper fibers Home and Building Control Home and Building Control Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...

Reviews: