L7124U UNIVERSAL OIL ELECTRONIC AQUASTAT® CONTROLLER
69-1232—2
6
TROUBLESHOOTING
When attempting to diagnose system performance,
references to the LED can help to identify specific areas
not working properly. The LED are:
PWR—ON indicates 24 Vac power present.
C—ON indicates circulator relay energized.
TSTAT—ON indicates thermostat call for heat.
ZC—ON indicates power to zoning.
B—ON indicates burner relay energized.
LL/DSBL—
• ON indicates Low Limit function selected.
• OFF indicates Low Limit disabled.
• Flashing indicates error. See Table 3 and
Troubleshooting Guide, Table 4.
Table 3. LED Error Codes.
.
Number
of Blinks
Cause
2
Sensor Error (Open or shorted sensor.)
3
System error(s); e.g., setpoint POT failure.
4
Safety relay has welded, device requires
replacement.
Table 4. Corrective Action .
System Condition
Check
Corrective Action
Boiler is cold, house is cold.
PWR LED Off
Check:
— 120 Vac system power.
— 1A fuse on L7124U.
PWR LED On
TSTAT LED Off
Check:
— Thermostat
— Thermostat wiring
PWR LED On
TSTAT LED On
B (burner) LED On
— Check:
— 120 Vac B1-B2.
— If no, replace burner relay.
— If yes, check burner and wiring.
PWR LED On
TSTAT LED On
LL/DSBL LED Flashing
Refer to LED diagnostics, Table 3.
Boiler is hot, house is cold.
PWR LED On
TSTAT LED On
C (circulator) LED On
Check:
— 120 Vac, C1-C2.
— If no, replace circulator relay.
— Check for circulation, air entrap-
ment, water flow.
— If yes, check circulator and wiring.
— Check for circulation, air entrap-
ment, water flow.
PWR LED On
TSTAT LED On
C (circulator), ZC (zone circulator)
LED Off
Check:
— Boiler below low limit temperature,
wait for boiler to above low limit
temperature.
PWR LED On
TSTAT LED On
ZC LED on
Check:
— Boiler above low limit.
— If yes, check for 120 Vac between
ZC and L2.
— If no, replace ZC relay .
— If yes, check switch relays, zone
circulators and wiring.