L7124U UNIVERSAL OIL ELECTRONIC AQUASTAT® CONTROLLER

69-1232—2

6

TROUBLESHOOTING

When attempting to diagnose system performance, 
references to the LED can help to identify specific areas 
not working properly. The LED are:

PWR—ON indicates 24 Vac power present.

C—ON indicates circulator relay energized.

TSTAT—ON indicates thermostat call for heat.

ZC—ON indicates power to zoning.

B—ON indicates burner relay energized.

LL/DSBL—

• ON indicates Low Limit function selected.
• OFF indicates Low Limit disabled.
• Flashing indicates error. See Table 3 and 

Troubleshooting Guide, Table 4.

Table 3. LED Error Codes.

.

Number 

of Blinks

Cause

2

Sensor Error (Open or shorted sensor.)

3

System error(s); e.g., setpoint POT failure.

4

Safety relay has welded, device requires 
replacement.

Table 4. Corrective Action .

System Condition

Check

Corrective Action

Boiler is cold, house is cold.

PWR LED Off

Check: 

— 120 Vac system power.
— 1A fuse on L7124U.

PWR LED On
TSTAT LED Off

Check:

— Thermostat
— Thermostat wiring

PWR LED On
TSTAT LED On
B (burner) LED On

— Check:
— 120  Vac  B1-B2.
— If no, replace burner relay.
— If yes, check burner and wiring.

PWR LED On
TSTAT LED On
LL/DSBL LED Flashing

Refer to LED diagnostics, Table 3.

Boiler is hot, house is cold.

PWR LED On
TSTAT LED On
C (circulator) LED On

Check:

— 120 Vac, C1-C2.
— If no, replace circulator relay.
— Check for circulation, air entrap-

ment, water flow.

— If yes, check circulator and wiring.
— Check for circulation, air entrap-

ment, water flow.

PWR LED On 
TSTAT LED On
C (circulator), ZC (zone circulator) 
LED Off

Check:

— Boiler below low limit temperature, 

wait for boiler to above low limit 
temperature.

PWR LED On
TSTAT LED On
ZC LED on

Check:

— Boiler above low limit.
— If yes, check for 120 Vac between 

ZC and L2.

— If no, replace ZC relay .
— If yes, check switch relays, zone 

circulators and wiring.

Summary of Contents for L7124U

Page 1: ... mechanical distance Some models also have a Low Limit and Low Limit Differential adjustment The range of the Low Limit dial is from 110 F to 220 F 43 C to 104 C Rotating the Low Limit potentiometer fully counterclockwise disables the low limit function and turns on the Low Limit Disabled LED The L7124U is designed for use with 24 Vac electronic and electromechanical thermostats and has screw type...

Page 2: ...e flange on the well 9 Securely tighten the clamp screw IMPORTANT Best thermal response is obtained with a well that snugly fits the sensor Insert the sensor until it rests against the bottom of the well use a well of correct length and bend the wiring if necessary to hold the bulb against the bottom of the well If the well is not a snug fit on the sensor use the heat conductive compound furnished...

Page 3: ...proved for use with copper wire only Follow the appropriate wiring diagrams shown on the inside of the front cover of the L7124U or in Fig 3 and 4 Fig 3 L7124U single zone connections SENSOR WIRES IMMERSION WELL CLAMP SCREW IMMERSION WELL CLAMP M16120 HEAT CONDUCTIVE COMPOUND OPTIONAL CONTROLLER CASE BOILER IMMERSION WELL SENSOR LOW LIMIT HIGH LIMIT DIFF SENSOR PWR T L2 T TSTAT DSBL LL B B2 B1 C2 ...

Page 4: ...CULATOR TO ADDITIONAL R845A RELAYS FOR OTHER ZONES LOW LIMIT HIGH LIMIT DIFF SENSOR PWR T L2 T TSTAT DSBL LL B B2 B1 C2 ZR ZC C1 C ZC 1 2 M17777 1 1 2 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONTROL CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED LINE VOLTAGE OIL BURNER RELAY LINE VOLTAGE CIRCULATOR LOW VOLTAGE THERMOSTAT T1 LEGEND LED SENSOR...

Page 5: ...he fixed differential 3 Low Limit Boiler temperature has gone below the low limit setting minus the low limit differential and has not gone above the low limit setting 4 Error The controller has detected an error condition e g open sensor and has shut down the burner output The circulator and ZC output are energized The controller continues to function and automatically restarts if the error condi...

Page 6: ...System Condition Check Corrective Action Boiler is cold house is cold PWR LED Off Check 120 Vac system power 1A fuse on L7124U PWR LED On TSTAT LED Off Check Thermostat Thermostat wiring PWR LED On TSTAT LED On B burner LED On Check 120 Vac B1 B2 If no replace burner relay If yes check burner and wiring PWR LED On TSTAT LED On LL DSBL LED Flashing Refer to LED diagnostics Table 3 Boiler is hot hou...