5
EN2C-0112SZ20 R0202
DIMENSIONAL DRAWING
62
52
119
25
7
8
27
104
8
Shaft Version
Nr.
5
6
PG 9
D
D
D) Fixing hole
through-hole 5,2 mm inside dia
Protection
•
IP 44, assuming appropriate cable entries and screw
fastening (DIN 40050)
Cable entries
• 2 x PG9
Cable connection
•
terminal block for 0.5 mm
2
(min.) and 2.5 mm
2
(max.)
wire cross-section
Direction of rotation
•
see “Type overview”
Torque and holding torque
•
see “Type overview”
Drive times
•
3 to 65 sec for 90
°
Limit and auxiliary switches
•
max. 7
operation with adjustable cam discs, cams coloured in
normal way:
blue
fully closed position
orange
low load
red
high load
black
spare switches for additional functions
•
switching voltage
AC 24....230 V
•
switching capacity
with inductive loads 250 VA
Ambient temperature
•
operation
0 ... +60
°
C
•
transport and storage
-20 ... +60
°
C
Condensation, icing and exposure to water not
permitted
Weight
• approx. 610g
A