PW7K1ICE Wiring and Setup
IT Security
PW7K1ICE Installation and Configuration Guide
, Document 800-26497
29
Note:
If this input is defined, every three seconds the LED is pulsed to its opposite
state for 0.1 seconds, otherwise, the LED is off.
2.15 IT Security
When installing the LP1501, it is important to ensure that it is done in a secure
manner.
Upon installation, the user accounts to the web configuration page should be created
with secure passwords, and that all DIP switches are in the off position for the normal
operating mode. The LP1501 is shipped from the factory with a default login account,
which is enabled when DIP 1 is moved from OFF to ON. The default login user name
and password will be available for five minutes once enabled. Therefore, it is
important that at least one user account is defined, and the DIP switches are set to OFF
before the LP1501 is commissioned. It is also highly recommended not to configure
the LP1501 with an IP address that is accessible from the public Internet.
To further enhance network security, options are available to disable SNMP, Zeroconf
discovery, as well as the web configuration module itself. Additionally, data
encryption can also be enabled over the host communication port.
2.16 Specifications
The interface is for use in low voltage, class 2 circuits only.
The installation of this device must comply with all local fire and electrical codes.
Power Input
• PoE Power Input 12.95W, compliant to IEEE 802.3af
- OR -
• PoE+ (25 W), compliant to IEEE 802.3at or 12 VDC+_10%, 1.8
A maximum
Power Output
• 12VDC @ 625mA including reader and AUX output
Power Output
• PoE+ or external 12 VDC: 12
VDC @ 1.25 A including
reader and Auxiliary Power
output
• Micro USB
Port
• 5 VDC maximum (deduct 270
mA from reader and Auxiliary
Power output)