Lyric Controller Installation and Reference Guide
- 35 -
Agency
Agency
Agency
Agency Notices
Notices
Notices
Notices
1.
For Residential Burglar Alarm installations with line security, total exit delay time must not exceed 60
seconds. For Burglar Alarm installations without line security, total exit delay time must not exceed 120
seconds.
2. Periodic testing must be at least every 24 hours.
3. Remote downloading without an alarm company technician on-site (unattended downloading) is not
permissible for ETL installations.
4. As SIA limits for delay of alarm reporting and sounding can exceed UL Standard limits for commercial and
residential applications, the following requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to a
remote monitoring location, or to delay the energizing of a local alarm sounding device to permit the
alarm system user to enter and disarm the system, or to arm the system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
SIA Quick Reference Guide
SIA Quick Reference Guide
SIA Quick Reference Guide
SIA Quick Reference Guide
Programming Section
Programming Section
Programming Section
Programming Section
Feature
Feature
Feature
Feature
Ra
Ra
Ra
Range
nge
nge
nge
Shipping Default
Shipping Default
Shipping Default
Shipping Default
SIA Requirement
SIA Requirement
SIA Requirement
SIA Requirement
Installation and Setup Guide or Programming Guide
Installation and Setup Guide or Programming Guide
Installation and Setup Guide or Programming Guide
Installation and Setup Guide or Programming Guide
Reporter
Reporter
Reporter
Reporter/
Report Selection
Exit Error
Not selectable
Enabled
Enabled
Recent Closing
Not selectable
Enabled
Enabled
Alarm Cancel
Enabled or Disabled
Enabled
Enabled
Reporter
Reporter
Reporter
Reporter/Options
Number of
Reports
1 to 6 Reports
2 Reports
2 Reports
Alarm Report
Delay (Abort
Window)
15, 30 and 45 seconds
30 seconds
30 seconds*
System Settings
System Settings
System Settings
System Settings
Entry Delay # 1
None, 15, 30, 45, 60 and
90 seconds and 2, 3 or
4 minutes
30 seconds
30 seconds minimum
Entry Delay # 2
None, 15, 30, 45, 60 and
90 seconds and 2, 3 or
4 minutes
30 seconds
30 seconds minimum
Exit Delay
45, 60, 90 seconds and
2 minutes
60 Seconds
45 seconds minimum
Restart Exit Time
Enabled or Disabled
Yes (Enabled)
Enabled
Exit Warning
Not selectable
Yes (Enabled)
Enabled
Auto Stay
Arming
Enabled or Disabled
Yes (Enabled)
Enabled
Cross Zone Delay
30 seconds and 2
minutes (in 30 second
increments), 3 minutes
and 4 minutes
None (Disabled)
Enabled and two zones
programmed
Zones
Zones
Zones
Zones
Fire Alarms
Zone Type “Fire with
Verification” must be
selected for Fire Zone
95
Disabled
Disabled
User Guide
User Guide
User Guide
User Guide
User Functions/
User Functions/
User Functions/
User Functions/
User Access
Duress
Duress Code is
Programmed by Master
User as User 48
Disabled
Disabled
System Functions/
System Functions/
System Functions/
System Functions/
Testing the System**
System Test
System tests provided
as a User Function
n/a
n/a
Communications
While the system is in
Test mode, no alarm
reports are sent to the
Central Station
Disabled
Disabled
* Combined Entry Delay and Alarm Report Delay (Abort Window) should not exceed 1 minute.
** Refer to the User Guide for procedures on Testing the System.