M7410E SMALL MODULATING LINEAR VALVE ACTUATOR

5

EN0B-0097GE51 R1004

Electric Wiring of Auxiliary Switches

The electrical installation must comply with the wiring
diagram shown in Fig. 10. If the auxiliary switch is connected
to 230 Vac, a switch with a contact gap of at least 3 mm for
each pole must be fitted with the installation.

DN 15,
DN 20

DN 25 -
DN 40

DN 15 -
DN 40

DN 15 -
DN 20

(230 Vac only):

M7410E

max. 5 (1)A

230 Vac:

max. 100 mA

24 Vac:

BLUE

BROWN

BLACK

BLUE

BROWN

BLACK

BLUE

BROWN

BLACK

BLUE

BROWN

BLACK

BLUE

BROWN

BLACK

BLUE

BROWN

BLACK

A

B

A

B

open

A

B

close

A

B

A

AB

B

A

AB

B

A

AB

B

A

AB

B

A

B

A

B

open

close

A

AB

B

open

close

A

AB

B

close

open

Fig. 10. Electric wiring of auxiliary switch

Application Example:

Switching Off an Electrical Appliance

2-Way-Valve

DN 15, DN 20

max. 5 (1)A

BLUE

BLACK

E. g. fan, pump etc.

Fig. 11. Electric wiring of auxiliary switch

All Other Valves

DN 15 - DN 40

DN 25 - DN 40

DN 15 - DN 20

max. 5 (1)A

BLUE

BLACK

E. g. fan, pump etc.

Fig. 12. Electric wiring of auxiliary switch

Summary of Contents for M7410E

Page 1: ... needed Due to an automatic synchronization function the close off point is self adjusting Based on a running time of 150 s valve positioning and flow adjustment is very exact Manual positioning is provided for all actuators The actuator is both attractive and robust in design A special version with auxiliary switch is available FEATURES Microprocessor based positioner ensures precise stem positio...

Page 2: ...nous motor through a set of gears A magnetic clutch limits the torque of the gear assembly and the driving force of the actuator The actuator is fixed to the valve body by means of a coupling ring requiring no tools for mounting The actuator is maintenance free and supplied completely with a ready to wire connecting cable A microprocessor based high performance positioner guarantees accurate contr...

Page 3: ...hand Do not use tools or additional force insofar as this may damage the actuator and valve Fig 3 Mounting the actuator SWITCH SELECTION The built in selector switches must be set according to the valve type 2 way or 3 way valve size and the controller output signal 0 10 V or 2 10 V see Fig 4 factory setting Y 0 10V Y 2 10V A B AB Y 10V opens A B Y 10V opens A B Y 10V closes factory setting 0 100 ...

Page 4: ...ement of the actuator stem AUXILIARY SWITCHES The actuators with the OS number M7410E4022 and M7410E4033 feature 2 auxiliary switches Each switch has its own cable Auxiliary switch S1 with fixed switchpoint when the stem position is in Auxiliary switch S2 with adjustable switchpoint when the stem position is out a c b a c b Fig 8 Auxiliary switch cables Adjustment of Auxiliary Switch 2 The auxilia...

Page 5: ...7410E max 5 1 A 230 Vac max 100 mA 24 Vac BLUE BROWN BLACK BLUE BROWN BLACK BLUE BROWN BLACK BLUE BROWN BLACK BLUE BROWN BLACK BLUE BROWN BLACK A B A B open A B close A B A AB B A AB B A AB B A AB B A B A B open close A AB B open close A AB B close open Fig 10 Electric wiring of auxiliary switch Application Example Switching Off an Electrical Appliance 2 Way Valve DN 15 DN 20 max 5 1 A BLUE BLACK ...

Page 6: ...öblinger Straße 17 D 71101 Schönaich Phone 49 7031 63701 Fax 49 7031 637493 http europe hbc honeywell com Subject to change without notice Printed in Germany Manufacturing location certified to EN0B 0097GE51 R1004 DIMENSIONS MM 49 100 60 58 Fig 13 Housing type B 49 109 87 82 Fig 14 Housing type C ...

Reviews: