Procedural Considerations
Page 28
34-ST-25-20 MC Toolkit User Manual Release
3
9/06
Input Calibration (De Transmitters) - Correct Input (Zero), LRV, URV; Reset Corrects
Correct
Input at
LRV
(ST 3000)
Select the
Correct LRV
button. This message appears.
Adjust the PV input pressure
to the
exact value of the LRV
entered
in the
DE
CONFIGURE
display.
Select the
OK
button; this
message appears.
Observe the input pressure
at the applied value; when
it is stable, select the
OK
button.
When the transmitter has
completed the LRV
correction, this message
appears.
Select
OK
to
acknowledge.
Correct
Input at
LRV
(STT 3000)
Select the
Correct LRV
button. This message appears.
Adjust the input
temperature to the
exact
value of the LRV
entered
in
the
DE CONFIGURE
display.
Select the
OK
button; this
message appears.
Select the
OK
button to
acknowledge
Correct
Input at
URV
(ST 3000)
Select the
Correct URV
button. This message appears.
Adjust the PV input
pressure to the
exact value
of the URV
entered
in the
DE CONFIGURE
display.
Select the
OK
button.
When the transmitter has
completed the URV
correction, this message
appears.
Select
OK
to
acknowledge.
Correct
Input at
URV
(STT 3000)
Select the
Correct URV
button. This message appears.
Adjust the input
temperature to the
exact
value of the URV
entered
in the
DE CONFIGURE
display.
Select the
OK
button; this
message appears.
Select the
OK
button to
acknowledge