Reference Data
Release 3
34-ST-25-20 MC Toolkit User Manual
77
9/06
Honeywell DE Fields and Values
Table 26 DE Fields and Values
Dialog
Field
Value
Device Info
Tag ID
Tag id (8 chars.)
Type
Transmitter
type
Firmware
version
Firmware
version of the transmitter
Serial number
Serial number of transmitter
Scratch pad
32 chars.
General PV
Type
Dual Range
(STDC)
Single Range
Single Range
w/SV
Communication mode
Analog
DE 4 byte
DE 6 byte
Failsafe
Direction
Upscale
Downscale
Line Filter (STT only)
50 Hz
60 Hz
T/C Fault Detect (STT only)
Enabled
Disabled
DE Configure
LRL, URL, LRV, URV
Floating point
PV Units (STT only)
°C
°F
K °R
PV Units (ST only)
InH2O @ 39F
InH2O @ 68F
MmHg @ 0C
Psi
KPa
MPa
mBar
bar
g/cm²
kg/cm²
inHg @ 32F
mmH2O @ 4C
mH2O @ 4C
ATM
InH2O @ 60F
SV
Units °C
°F
Sensor Type (STT only)
T/C J
T/C K
T/C T
T/C S
T/C R
T/C E
T/C B
T/C N
RTD-PT100J
Millivolts
RTD-PT100D
RTD-PT200
RTD-PT500
RTD-Ni500
RTD-Cu10
RTD-Cu25
T/C–RH
Radiamatic
T/C–W5W26
T/C–W3W25
Ohms
T/C-NiNiMo
Sensor Type (ST only)
DP
AP
GP
Damping
(STT
only)
0.00
0.30
0.70
1.50
3.10
6.30
12.70
25.50
51.10
102.30
DE Configure
(continued)
Damping (ST only)
0.00
0.16
0.32
0.48
1.00
2.00
4.00
8.00
16.0
32.0