background image

R7426D UNIVERSAL INPUT CONTROLLER

5

EN1B-0204GE51 R0403

CONFIGURATION SETTINGS

All configuration parameters have to be set to select the

correct control functions as required for the job application.

Direct - Reverse Action Dir/RevY1 (C.01)

The output action of the analog output must sometimes be

reversed for a correct opening and closing direction of the

valve or damper. This depends on whether the output

controls a 2-way or 3-way valve or on the direction the

damper shaft moves to open the damper (cw or ccw). It is

only needed, if the actuator does not provide a direction

selector switch, plug or similar.

Note: 

The analog output signal Y1 can be displayed in the

standard display mode. The selected action of

signal Y1 does not influence the display indication.

Control Point / Setpoint Adjustment CPATYP

(C.05)

The control point or setpoint can be adjusted via the internal

or an external potentiometer connected to the CPA/SPA

input. The potentiometer type is selected by 

CPATYP 

(see

Table 3).

Output Control Range Selection

YRange (C.06)

YRange

 is required to select the output control range

(0...100%) to either 2...10Vdc (

YRange

 = 0) or 0...10Vdc

(

YRange

 = 1).

Supply of Input Signal X2ext (C.12)

X2ext

 has to be set to 1, if the sensor input X1 is also used

for high or low limit control. This interconnects the X1 and X2

input internally and the sensor has to be connected only to

the X1 input.

When using a limit sensor X2, the parameter 

X2ext 

has to be

set to 0 (default). If sensor X2 is not used, the input has to be

deactivated by setting 

X2ext

 to 2.

Limit Type LimTyp (C.13)

 

LimTyp

 allows the selection of high or low limit control. High

limit control is performed if 

LimTyp

 = 1 and low limit control is

performed if 

LimTyp

 = 0.

Sensor Type Senstyp (C.14)

Three different sensor types can be used on input T3 with the

controller (see Table 5).

Automatic

identification

of sensor type

Temperature

range

Characteristics

Pt 1000

-30....+130

°

C

1000

 at 0

°

C

BALCO 500

-30....+130

°

C

500

 at 23.3

°

C

NTC 20k

-30....+85

°

C /

-30....+130

°

C

1)

20k

 at 25

°

C

1) 

NTC sensor is detected automatically, if during power up

the sensor temperature is within -30....+85

°

C and

Senstyp

 = 0.

NTC sensor is selected manually, if 

Senstyp

 is set to 1.

Table 5. Sensor Types

Automatic identification of sensor type is selected, if 

Senstyp

= 0 (default). After power up reset the controller detects auto-
matically the type of sensor, which is connected to the tem-
perature input T3. For a correct auto detection, it is
necessary that the measured temperature is in the specified
range (see Table 5).

Output Control Function Y1CTRF (C.15)

The R7426D controller performs direct control behaviour, if

Y1CTRF

 is set to 0. A rise in the measured variable will

increase the output value from 0...100% (direct acting). The

control action must be reversed for reverse control behavior

by setting 

Y1CTRF

 to 1. A rise in the measured variable will

decrease the output value (100..0%).

Note: 

The analog output signal Y1 with the selected con-

trol behavior is displayed in % in the standard

display mode.

Serial Communication Address Adr(C.22)

The parameter 

Adr

 sets the serial communication address,

used for controller start-up, service or maintenance purposes

via the bus.

Default Programming DefProg (C.23)

Setting 

DefProg

 to 1 resets all control and configuration

parameters to defaults (see Table 3 and Table 4). Default

programming is indicated by a display of 

def

.

After default programming, the parameter 

DefProg

 is reset to

0.

Span Adjustment

UStartPoint / UendPoint (C.24 / C.25)

The universal inputs X1 and X2 accept any analog inputs

within the range of 0...10Vdc and provides an input span

adjustment to match the range of the connected transmitters.

The start / end point of the input span can be adjusted by the

parameters 

UStartPoint

 / 

UendPoint

 and is converted to a

0...100% input range.

The parameters 

UStartPoint 

and 

UEndPoint

 are common

for both inputs X1 and X2.

Summary of Contents for MicroniK 200 R7426D

Page 1: ...y separated from the main power supply relays or other equipment which can possibly generate electromagnetic inter ference Verify that the ambient temperature and the humidity at the controller will be within the limits of 0 50 C 32 122 F and 5 to 95 rh Use shielded wiring in areas with high EMI All wiring should be separated from power lines by at least 150mm 6 Do not install controllers near fre...

Page 2: ...ac and controller 24Vac 2 Connect line power conductors to transformer primary Line power must be supplied from a breaker panel with dedicated controller circuit Do not turn the line power on until all wiring has been checked against job drawings 3 Connect transformers 24Vac secondary to the controller terminals 18 and 19 Connect one conductor to terminal marked 24V and the other to terminal marke...

Page 3: ...n type determines whether the limit function is low or high 1 0 1 Low limit High limit C 14 Senstyp Sensor type determines automatic detection or manual selection of NTC sensor type 0 0 1 Auto detection T3 NTC sensor type T3 C 15 Y1CTRF Control function 1 0 1 Direct control behaviour Reverse control behaviour C 22 Adr 1 Sets the serial communication address used for service or maintenance 254 0 25...

Page 4: ...2 Throttling range cascade or limit control loop for X2 1 50 10 0 5 P 12 tr1 1 Reset time main control loop Off 20sec 20min Off 10 0 5 sec min P 13 tr2 1 Reset time cascade control loop Off 20sec 20min Off 10 0 5 sec min P 15 Ystart Start point for mid range shift of output Y1 50 50 0 0 5 P 17 X1Cal Calibration of input X1 20 20 0 0 1 P 18 X2Cal Calibration of input X2 20 20 0 0 1 P 19 T3Cal Calib...

Page 5: ...utomatic identification of sensor type Temperature range Characteristics Pt 1000 30 130 C 1000Ω at 0 C BALCO 500 30 130 C 500Ω at 23 3 C NTC 20kΩ 30 85 C 30 130 C 1 20kΩ at 25 C 1 NTC sensor is detected automatically if during power up the sensor temperature is within 30 85 C and Senstyp 0 NTC sensor is selected manually if Senstyp is set to 1 Table 5 Sensor Types Automatic identification of senso...

Page 6: ...nt CTRP1 the submaster setpoint Wcas is automatically altered CTRP2 Cascade control is disabled if the submaster setpoint Wcas is set to Off Low limit of CTRP2 is performed if control parameter LimTyp 0 and high limit of CTRP2 is performed if control parameter LimTyp 1 Reset Span Adjustment Rcas P 07 The reset span adjustment Rcas determines the reset effect in the submaster setpoint Wcas is alter...

Page 7: ...ime Tu in discharge air control is normally in the range of 0 1 to 0 6min which allows adjustments of the reset time tr in a range of 0 2 to 2min In room control the response time Tu is in the range of 0 5 to 5min which results in a setting of 1 to 15min Derivative Decay Time td and Amplification vd P 27 P 28 The Proportional Integral Derivative P I D control adds the derivative function to P I co...

Page 8: ...defines the start point of summer or winter compensation Above the compensation changeover point Wcomp summer compensation and below Wcomp winter compensation is performed Summer Winter Compensation Authority Su Wi P 04 P 05 These authority settings determine the reset effect TComp of the compensation sensor T3 on the main setpoint W1 in percentages To calculate winter and summer authority for e g...

Page 9: ...e selected parameter or configuration no and enters the adjustment mode Fig 8 which is used to adjust configuration parameter values After adjustment the controller returns to selection mode by pushing the SET or SEL button Pushing the SEL button leads back to standard display mode Pushing the SET and SEL button simultaneously for approximately 1 sec the controller leaves the standard display mode...

Page 10: ...six actual values can be selected and displayed Fig 6 by pushing the SEL button The icons of the permanently displayed controller mode are described in the following table Controller Mode Status Display Off Off icon On Sun icon A A Main Input X1 Main Setpoint CTRP1 Limitation Cascade Input X2 Submaster Limit Setpoint CTRP2 Compensation Temperature T3 Output Y1 SEL SEL SEL SEL SEL SEL Fig 6 Standar...

Page 11: ...r decrements the value of the selected parameter Parameter ranges are shown in Table 3 and Table 4 An adjustment example is shown in Fig 12 Pushing the SEL button retains the old parameter value Pushing the SET button accepts the parameter value and returns to parameter configuration selection mode Resetting Parameter Values to Default Values Pushing simultaneously the or button during the power u...

Page 12: ...he nominal control range as shown in Fig 6 To return to output selection mode three options are available Pushing the SET button after adjustment activates the manual override fixing of output value Pushing the SEL button causes that the output value is still determined by the control loop no fixing To release the manual override fixed of the output enter output adjustment mode and push the and bu...

Page 13: ... or 1 CPA value 0 for CPATYP 2 SPA value control parameter W1 Standard Display and and and Main Sensor X1 is defective Limitation or Cascade Sensor X2 is defective Compensation Temperature Sensor T3 is defective T3 is displayed in X1 and X2 is displayed in Display if during power up no sensor is connected Display after error identification during operation Standard Display SEL SEL SEL SEL Fig 11 E...

Page 14: ...ntrol Solutions Honeywell AG Böblinger Straße 17 D 71101 Schönaich Phone 49 7031 63701 Fax 49 7031 637493 http europe hbc honeywell com Subject to change without notice Printed in Germany Manufacturing location certified to 7157 585 EN1B 0204GE51 R0403 ...

Reviews: