Electrical Connection
Midas-M can be powered by either 24 VDC via traditional discrete wiring or by approximately 48
VDC delivered through the Ethernet cable from a PoE source. In either case, the 4-20 mA analog
output can be used.
The analog output can be configured for fully isolated operation. With 24 VDC power the 4-20
mA output can be configured for sink, source or isolated output operations. Following are some
schematic diagrams of typical electrical connection configuration.
NOTE
When wiring the Midas-M Transmitter to a controller, program the controller for a 1-2
second delay before reporting to prevent false alarms.
Generic example Midas-M 3-wire sourcing
Midas-M
23
User Manual