Wiring The Relay Module
The Midas-M relay module contains:
Nine relays to activate external devices.
Eight gas alarm relays which indicate level 1 and level 2 alarms of each channel.
A common fault relay which indicate maintenance fault or instrument fault.
Power Supply
No separated power supply required Supplied from the Midas-M
transmitter
Power
consumption
< 1.45 W
Relay rating
1.0 A @ 30VDC or 0.5 A @ 125 VAC max, 10 uA @ 10 mV minimum
Wiring
14 AWG maximum per each channel
Specifications