PRODUCT DATA

® U.S. Registered Trademark
Copyright © 2003 Honeywell International Inc.
 All Rights Reserved 

N314

63-2540-9

ML4105, ML4115, ML8105, ML8115

Fast-Acting, Two-Position Actuators

FOR FIRE/SMOKE CONTROL APPLICATIONS

APPLICATION

The ML4105, ML4115, ML8105, and ML8115 Fast-Acting, 

Two-Position Actuators are spring return direct coupled 

actuators (DCA) with an integral junction box for on/off 

damper control. The actuator accepts an on/off signal from a 

single-pole, single-throw (spst) controller. Models are 

available with clockwise (cw) or counterclockwise (ccw) spring 

return and are designed to operate reliably in smoke control 

systems requiring Underwriter’s Laboratories Inc. UL555S 

ratings up to 350°F.

FEATURES

• 30 lb-in. (3.4 N•m) or 50 lb-in. (5.7 N•m) minimum 

driving torque at 350°F (176°C).

• Integral spring return ensures level of return torque.
• Fifteen-second spring return timing.
• No special cycling required during long-term holding. 

(See Operation section.)

• No audible noise during holding.
• Patent pending design eliminates need for limit 

switches to reduce power consumption.

• Models available for 24, 120, and 230 Vac.
• Ninety-five degree angle of rotation.
• Actuator holds rated torque at reduced power level.
• Die-cast aluminum housing.
• Housing design allows flush mounting to damper.
• Integral junction box with three conduit openings 

eliminates need for separate wiring box.

• High-temperature indicator included.

APPLICABLE LITERATURE

— Motor/Actuator Selection Guide 

for Damper Applications

63-8419

— Engineering Manual of Automatic Control

(also called The Gray Manual)

77-1100

— Direct Coupled Actuator 

Quick Selection Guide

63-8553

— Damper Torque Calculator

63-8437

Contents

Application ........................................................................

1

Features ...........................................................................

1

Applicable Literature .........................................................

1

Specifications ...................................................................

2

Ordering Information  ........................................................

2

Installation ........................................................................

4

Operation ..........................................................................

6

Checkout ..........................................................................

6

Summary of Contents for ML4105

Page 1: ...al spring return ensures level of return torque Fifteen second spring return timing No special cycling required during long term holding See Operation section No audible noise during holding Patent pending design eliminates need for limit switches to reduce power consumption Models available for 24 120 and 230 Vac Ninety five degree angle of rotation Actuator holds rated torque at reduced power le...

Page 2: ...28 UNF set screws Use 1 8 in Allen wrench to tighten set screws ML4105C D Four 3 mm set screws Use 3 mm Allen wrench to tighten set screws ML4115 ML8115 Two 1 4 28 UNF set screws Use 1 8 in Allen wrench to tighten set screws IMPORTANT Honeywell does not recommend using linkages with these actuators because side loading of the output hub reduces actuator life Temperature Ratings Ambient 0 F to 130 ...

Page 3: ...ication NFPA recommends periodic examination of each fire smoke damper semi annually or annually to ensure proper performance Design Life at Rated Voltage 60 000 full stroke cycles Approvals See Table 2 Environmental Protection Ratings See Table 3 Accessories 201391 Shaft Adapter for 3 8 in shafts not supplied with actuator 205649 Mounting Bracket not supplied with actuator Table 2 Approvals Table...

Page 4: ... the bottom that with a 205649 Mounting Bracket secure it flush to a damper box see Fig 2 When mounted correctly these slots allow the actuator to float without rotating relative to the damper shaft CAUTION Equipment Damage Hazard Tightly securing actuator to damper housing can damage actuator Mount actuator to allow it to float along its vertical axis NOTE ML4105 ML4115 ML8105 and ML8115 Actuator...

Page 5: ... lb in maximum 60 lb in torque Use 1 8 in or 3 mm Allen wrench see Specifications for details to tighten set screws Wiring See Fig 4 through 8 for typical wiring diagrams WARNING Electrical Power Hazard Line voltage can cause death or serious injury and short equipment circuitry Disconnect power supply before installation CAUTION Electrical Shock or Equipment Damage Hazard Low voltage can shock in...

Page 6: ... building IMPORTANT If the indicator turns black replace the actuator NOTE The actuator is designed to operate for 30 minutes during a one time excursion to 350 F 176 C CHECKOUT ML4105A B and ML4115A B 120 Vac model 1 Verify that the indicator has not turned black see Temperature Indicator section 2 Check damper position 3 Connect 120 Vac to the black and white leadwires to drive the damper to the...

Page 7: ... DK Installasjonsinstruks N Installationsinstrukioner SF Asennusohje S Installations Instrukioner E Instrucciones de montage M11874 ASSEMBLY EINBAU MONTAGE MONTAGGIO MONTAGE MONTERE MONTERING ASENTAMINEN MONTERA MONTAJE D F I NL DK N FIN S E 24 VAC 120 VAC M11875 b a M11876 a b c d M12030 a b M11881 b a M11882 HEX 4mm MIN 45 lb in 5 1 Nm MAX 60lb in 6 8 Nm a b c A A1 A4 A3 A5 A2 A6 ...

Page 8: ...Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario 17 Changi Business Park Central 1 Belgium Suite 200 M1V 4Z9 Singapore 486073 Sunrise FL 33325 National Fire Codes is a registered trademark of the National Fire Protection Association NFPA 24 VAC 120 VAC M11884 DISASSEMBLY AUSBAU DÉMONTAGE SMONTAGGIO DEMONTAGE AFM...

Reviews: