background image

ML4125, ML4135, ML8125, ML8135 FAST-ACTING, TWO-POSITION ACTUATORS

63-2567—3

6

OPERATION

The actuators are operated by an spst two-position controller. 
When using an spst two-position controller, the actuator drives 
to the damper fully open position when controller contact 
makes and spring returns to the damper fully closed position 
when controller contact breaks. The actuator drops to holding 
power level on detection of stall, independent of hub position.

If power fails, the actuator spring returns to the 0° position.

CHECKOUT

ML4125A,B, ML4135 (120 Vac model)

1.

Check damper position.

2.

Connect 120 Vac to the black and white leadwires to 
drive the damper to the open position. The actuator 
should drive the damper.

3.

If the actuator does not run, remove power for at least 
two seconds.

4.

If the actuator spring returns, allow it to close entirely, 
then return to step 2.

5.

If the actuator does not spring return, verify that the 
actuator is properly installed. See Installation section.

6.

If the actuator is correctly installed but neither runs nor 
spring returns, replace the actuator.

ML4125C,D (230 Vac model)

1.

Check damper position.

2.

Connect 230 Vac to the blue and brown leadwires to 
drive the damper to the open position. The actuator 
should drive the damper.

3.

If the actuator does not run, remove power for at least 
two seconds.

4.

If the actuator spring returns, allow it to close entirely, 
then return to step 2.

5.

If the actuator does not spring return, verify that the 
actuator is properly installed. See Installation section.

6.

If the actuator is correctly installed but neither runs nor 
spring returns, replace the actuator.

ML8125, ML8135 (24 Vac model)

1.

Check damper position.

2.

Connect 24 Vac to the red and black leadwires to drive 
the damper to the open position. The actuator should 
drive the damper.

3.

If the actuator does not run, remove power for at least 
two seconds.

4.

If the actuator spring returns, allow it to close entirely, 
then return to step 2.

5.

If the actuator does not spring return, verify that the 
actuator is properly installed. See Installation section.

6.

If the actuator is correctly installed but neither runs nor 
spring returns, replace the actuator.

Summary of Contents for ML4125

Page 1: ...e range No audible noise during holding Electronic circuitry provides efficient operation while eliminating the need for limit switches Ninety five degree angle of rotation Die cast aluminum housing Housing design allows flush mounting to damper Integral junction box with three conduit openings eliminates need for separate wiring box Direct mounting to 3 8 or 1 2 in round or square shaft ML4125 ML...

Page 2: ...W Holding 0 11A 9W ML8125 Running 15 6 VA Holding 4 VA ML8135 Running 18 VA Holding 8 5 VA Temperature Ratings Ambient 40 F to 130 F 40 C to 55 C Shipping and Storage 40 F to 140 F 40 C to 60 C Humidity Ratings 5 to 95 RH noncondensing Electrical Connections ML4125A B ML4135 ML8125 ML8135 Two color coded 16 in leads includes ground screw ML4125C D 1m appliance cable Three 7 8 in holes for conduit ...

Page 3: ...25 seconds load dependant Spring Close ML4125 ML8125 20 to 25 seconds ML4135 ML8135 15 seconds Design Life at Rated Voltage ML4125 ML8125 80 000 full stroke cycles ML4135 ML8135 60 000 full stroke cycles Environmental Protection Ratings See Table 2 Table 2 Environmental Ratings Approvals See Table 3 Accessories 201391 Shaft Adapter for 3 8 in 10 mm shafts 205649 Mounting Bracket included with the ...

Page 4: ...axis The actuators are designed to open a damper by driving the damper shaft in either clockwise or counterclockwise direction The actuator housing has two slots on the bottom that with a 205649 Mounting Bracket secure it flush to a damper box see Fig 2 When mounted correctly these slots allow the actuator to float without rotating relative to the damper shaft NOTE ML4125 ML4135 ML8125 and ML8135 ...

Page 5: ...aft using minimum 30 lb in maximum 60 lb in torque Use 1 8 in or 3 mm Allen wrench see Specifications for details to tighten set screws Wiring WARNING Electrical Power Hazard Line voltage can cause death or serious injury and short equipment circuitry Disconnect power supply before installation CAUTION Electrical Shock or Equipment Damage Hazard Low voltage can shock individuals or short equipment...

Page 6: ... If the actuator is correctly installed but neither runs nor spring returns replace the actuator ML4125C D 230 Vac model 1 Check damper position 2 Connect 230 Vac to the blue and brown leadwires to drive the damper to the open position The actuator should drive the damper 3 If the actuator does not run remove power for at least two seconds 4 If the actuator spring returns allow it to close entirel...

Page 7: ...Installasjonsinstruks N Installationsinstrukioner SF Asennusohje S Installations Instrukioner E Instrucciones de montaje M11874 ASSEMBLY EINBAU MONTAGE MONTAGGIO MONTAGE MONTERE MONTERING ASENTAMINEN MONTERA MONTAJE D F I NL DK N FIN S E 24 VAC 230 VAC M11876 a b c d M11876 M11875 b a M11881 b a M11882 a b c HEX 4mm MIN 45 lb in 5 1 Nm MAX 60lb in 6 8 Nm A A1 A4 A3 A5 A2 A6 M12030 a b ...

Page 8: ...eywell Honeywell Limited Honeywell Limitée Room 3213 3225 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Sun Hung Kai Centre 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario No 30 Harbour Road Belgium Suite 200 M1V 4Z9 Wanchai Sunrise FL 33325 Hong Kong 24 VAC 230 VAC DISASSEMBLY AUSBAU DÉMONTAGE SMONTAGGIO DEMONTAGE AFMONTERE DEMONTERE ...

Reviews: