background image

ML6421, ML7421 NON-SPRING RETURN ELECTRIC LINEAR VALVE ACTUATORS

63-2515—4

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or 

phone:

1.

Your local Home and Building Control Sales Office (check white pages of your phone directory).

2.

Home and Building Control Customer Relations

Honeywell, 1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONS

Models:

Dimensions: 

 See Fig. 1.

Weight: 

 5.1 lb (2.3 kg).

Electrical Ratings:

Power Input: 24 Vac (+10%, -15%), 60 Hz.

Power Consumption: 11 VA maximum at 24 Vac.

Signal Inputs:

ML6421:

24 Vac across T1 and W: Drives stem downward.

24 Vac across T2 and B: Draws stem upward.

ML7421: 0 to 10 Vdc or 2 to 10 Vdc.

Actuator Material:

Cover: ABS plastic.

Yoke and Base: Diecast aluminum.

Stem Force: 

 405 lbf (1800N).

Close-off Pressure Ratings: 

 See Table 1.

Cable Entry: 

 Two knockout holes for 1/2 in. conduit standard 

on actuator case.

Ambient Ratings:

Temperature:

Ambient Range: 14°F to 122°F (-10°C to +50°C).
Storage Range: -40°F to +158°F (-40°C to +70°C).

Humidity Range: 5 to 95 percent relative humidity, 

noncondensing.

Approvals:

Canadian Standards Association Listed.

Underwriter’s Laboratories, Inc. UL94-5V Flame Retardant 

(file E181716).

Meets CE requirements.

Protection Standard: 

 IP54.

Accessories:

43191679-101 Single Auxiliary Potentiometer for ML6421A.

43191679-102 Single Auxiliary Potentiometer for ML6421B.
43191679-103 Dual Auxiliary Potentiometer for ML6421A.

43191679-104 Dual Auxiliary Potentiometer for ML6421B.

43191680-102 Dual Auxiliary Switch (for 24 Vac use 

only

).

43196000-001 High Temperature Kit (for actuators with 3/4 in. 

stroke). Increases maximum temperature to 428°F (220°C).

43196000-102 High Temperature Kit (for actuators with 1-1/2 in. 

stroke). Increases maximum temperature to 428°F (220°C).

Table 1. Close-off Ratings for ML6421, ML7421 Electric Linear Valve Actuators and Honeywell Valves (psi).

a

For use with ML6421B or ML7421B Actuators only.

b

Represents maximum pressure difference between the outlet and either of the two inlets.

c

Do not exceed 100 psi with V5011G valves used in steam applications.

d

Rating is for steam at maximum 100 psi. Ratings for water applications are the same as for the V5011N1xxx.

Model

Stroke in 

in. (mm)

Run Time in 

sec at 60 Hz

Description

ML6421A

3/4 (20)

95

Electric Linear 

Valve Actuator

ML7421A
ML6421B

1-1/2 (38)

175

ML7421B

Type

Valve

1/2 in. 3/4 in. 1 in. 1-1/4 in. 1-1/2 in. 2 in. 2-1/2 in. 3 in. 4 in.

a

5 in.

a

6 in.

a

Flange V5011A,B,C

77

53

29

18

12

V5011B

V3350/51/60/61;V3450/51/60/61

63

b

45

b

25

b

16

b

11

b

NPT

V5011F,G

150

c

150

c

150

c

150

c

150

c

150

c

100

61

V5011N1xxx, V5011N3xxx, 

V5013N

230

230

230

230

230

126

V5011N2xxx

100

d

100

d

100

d

100

d

100

d

100

d

V5013F

150

150

150

150

150

150

Summary of Contents for ML6421

Page 1: ...tput of 0 to 10 Vdc or 2 to 10 Vdc These actuators operate standard Honeywell valves in HVAC applications An internal selector plug can be used to reverse the direction of action FEATURES Quick and easy installation No separate linkage required 3 4 in 20 mm stroke on ML6421A and ML7421A 1 1 2 in 38 mm stroke on ML6421B and ML7421B No adjustments required Accurate valve positioning Low power consum...

Page 2: ...nge 40 F to 158 F 40 C to 70 C Humidity Range 5 to 95 percent relative humidity noncondensing Approvals Canadian Standards Association Listed Underwriter s Laboratories Inc UL94 5V Flame Retardant file E181716 Meets CE requirements Protection Standard IP54 Accessories 43191679 101 Single Auxiliary Potentiometer for ML6421A 43191679 102 Single Auxiliary Potentiometer for ML6421B 43191679 103 Dual A...

Page 3: ...uct operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation Location Install the actuator in a location that allows enough clearance for mounting accessories and for servicing CAUTION Equipment Damage Hazard Can damage actuator due to condensation or a valve gland ...

Page 4: ...emoving actuator cover Wiring CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation IMPORTANT 1 All wiring must comply with local electrical codes ordinances and regulations 2 Voltage and frequency of the transformer used with the actuator must correspond with the characteristics of the power supply and th...

Page 5: ...ons WIRING STRIP T1 T2 W B 1 L1 HOT L2 W R W B T Y G R B SPDT ML6421A B 2 3 POWER SUPPLY PROVIDE DISCONNET MEANS AND OVERLOAD PROTECTION AS REQUIRED ALL WIRING BLOCKS HAVE THE SAME NUMBER OF TERMINALS 8 BUT THE ONLY TERMINALS THAT ARE ACTIVE ON THIS BLOCK ARE T1 W AND B THE R W B AND T Y G TERMINALS ARE A SIX TERMINAL WIRING BLOCK SEPARATE FROM THE MAIN BLOCK THEY DO NOT APPEAR ON ALL MODELS BECAU...

Page 6: ...ase the spindle one turn by turning the manual operator knob This will ensure automatic disengagement of the manual operator upon power resumption NOTE If the manual operator knob is not pushed in while turned it will rotate only a short distance before disengaging without power resumption Fig 10 Manual operator knob ML7421 Signal Input Failure Using selector plug W1 the actuator can be set to run...

Page 7: ...e leadwires to move the valve in the required direction 4 If the actuator does not move make sure the actuator is properly installed 5 If the actuator is correctly installed and does not run replace the actuator Controller Checkout 1 Adjust the setpoint of the controller to call for opening or closing the valve Observe the actuator 2 If the valve is closed it should begin to open 3 If the valve re...

Page 8: ...al Honeywell Europe S A Honeywell Latin American Honeywell Honeywell Limited Honeywell Limitée Control Products 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario 17 Changi Business Park Central 1 Belgium Suite 200 M1V 4Z9 Singapore 486073 Sunrise FL 33325 ...

Reviews: