background image

ML6421, ML7421 NON-SPRING RETURN ELECTRIC LINEAR VALVE ACTUATORS

7

63-2515—4

Actuator Override

To override the control signal (for freeze protection or similar 

applications), connect the 24 Vac common (T2) to either 

terminal O1 or O2. Connecting to terminal O1 fully extends 
the actuator stem. Connecting to O2 fully retracts the actuator 

stem.

The control signal (+) is ignored when the override signal is 

applied to terminal O1 or O2. This override can be achieved 

with a switch or a relay. See Fig. 12.

Direction of Action

The direction of action can be changed by repositioning the 
selector plug W3.

Fig. 12. Connections for overriding control signal to drive 

actuator to a specific position.

CHECKOUT

The actuator can be checked out either directly or using a controller.

Direct Checkout

1.

Mount the actuator for the required application.

2.

Check the valve position and make sure that 24 Vac is 
correctly applied to the actuator.

3.

Apply the control signal to the appropriate leadwires to 

move the valve in the required direction.

4.

If the actuator does not move, make sure the actuator is 

properly installed.

5.

If the actuator is correctly installed and does not run, 
replace the actuator.

Controller Checkout

1.

Adjust the setpoint of the controller to call for opening or 

closing the valve. Observe the actuator.

2.

If the valve is closed, it should begin to open.

3.

If the valve remains closed, move the setpoint further 

toward the open setting.

4.

If the valve does not move, check for 24 Vac in the 

actuator power input.

5.

If 24 Vac is present and the actuator does not operate, 
reverse the controller leadwires to determine if the 

device is incorrectly wired.

6.

If wiring is correct, 24 Vac is present on the power input 
terminals, and the actuator does not run, replace the 

actuator.

POWER SUPPLY. PROVIDE DISCONNECT MEANS 
AND OVERLOAD PROTECTION AS REQUIRED.

F

+

0-10Vdc OR 2-10 Vdc CONTROL SIGNAL. SEE SIGNAL 
INPUT (+) SECTION.

SEE OVERRIDE SECTION FOR DETAILS ON 
OVERRIDE OPERATION.

2-10 Vdc FEEDBACK SIGNAL. SEE OUTPUT SIGNAL 
FEEDBACK SECTION.

ML7421

WIRING
STRIP

F

+

T2

T1

O1

O2

1

3

4

2

INPUT

(FEEDBACK)

OUTPUT

3

2

SP3T

OVERRIDE

SWITCH

4

1

L1 
(HOT)

L2

M17438

Summary of Contents for ML6421

Page 1: ...tput of 0 to 10 Vdc or 2 to 10 Vdc These actuators operate standard Honeywell valves in HVAC applications An internal selector plug can be used to reverse the direction of action FEATURES Quick and easy installation No separate linkage required 3 4 in 20 mm stroke on ML6421A and ML7421A 1 1 2 in 38 mm stroke on ML6421B and ML7421B No adjustments required Accurate valve positioning Low power consum...

Page 2: ...nge 40 F to 158 F 40 C to 70 C Humidity Range 5 to 95 percent relative humidity noncondensing Approvals Canadian Standards Association Listed Underwriter s Laboratories Inc UL94 5V Flame Retardant file E181716 Meets CE requirements Protection Standard IP54 Accessories 43191679 101 Single Auxiliary Potentiometer for ML6421A 43191679 102 Single Auxiliary Potentiometer for ML6421B 43191679 103 Dual A...

Page 3: ...uct operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation Location Install the actuator in a location that allows enough clearance for mounting accessories and for servicing CAUTION Equipment Damage Hazard Can damage actuator due to condensation or a valve gland ...

Page 4: ...emoving actuator cover Wiring CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation IMPORTANT 1 All wiring must comply with local electrical codes ordinances and regulations 2 Voltage and frequency of the transformer used with the actuator must correspond with the characteristics of the power supply and th...

Page 5: ...ons WIRING STRIP T1 T2 W B 1 L1 HOT L2 W R W B T Y G R B SPDT ML6421A B 2 3 POWER SUPPLY PROVIDE DISCONNET MEANS AND OVERLOAD PROTECTION AS REQUIRED ALL WIRING BLOCKS HAVE THE SAME NUMBER OF TERMINALS 8 BUT THE ONLY TERMINALS THAT ARE ACTIVE ON THIS BLOCK ARE T1 W AND B THE R W B AND T Y G TERMINALS ARE A SIX TERMINAL WIRING BLOCK SEPARATE FROM THE MAIN BLOCK THEY DO NOT APPEAR ON ALL MODELS BECAU...

Page 6: ...ase the spindle one turn by turning the manual operator knob This will ensure automatic disengagement of the manual operator upon power resumption NOTE If the manual operator knob is not pushed in while turned it will rotate only a short distance before disengaging without power resumption Fig 10 Manual operator knob ML7421 Signal Input Failure Using selector plug W1 the actuator can be set to run...

Page 7: ...e leadwires to move the valve in the required direction 4 If the actuator does not move make sure the actuator is properly installed 5 If the actuator is correctly installed and does not run replace the actuator Controller Checkout 1 Adjust the setpoint of the controller to call for opening or closing the valve Observe the actuator 2 If the valve is closed it should begin to open 3 If the valve re...

Page 8: ...al Honeywell Europe S A Honeywell Latin American Honeywell Honeywell Limited Honeywell Limitée Control Products 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario 17 Changi Business Park Central 1 Belgium Suite 200 M1V 4Z9 Singapore 486073 Sunrise FL 33325 ...

Reviews: